VR2R-0368
① SA Source
- Source: 開啟完整 SA 文章
- Section:
Compute Tray: Thermal - Line hint:
485
Context Before
Our VR NVL72 Component BoM and Power Budget Model ↗ has provides the $ content breakdown of high end CCL and PCB content for VR NVL72 vs GB200/GB300.
Compute Tray: Thermal
Evidence
VR NVL72 takes liquid cooling to the next level. The VR NVL72 compute tray is 100% liquid cooled, whereas GB200 and GB300 compute trays adopt a hybrid of 85% liquid cooling and 15% air cooling. As a result of this, fans are removed from the compute tray and the cold plate coverage increases to remove heat from the front half of the chassis. An internal manifold will be placed in the middle of the chassis to distribute inlet coolant to the various modules and to collect the outlet coolant. Each of the modules within the compute tray will have a cold plate module attached. Each cold plate module connects to the internal manifolds via MQD (a smaller form factor quick disconnect specification standard by Nvidia for compact area application within the compute tray).
Context After

Source: Nvidia VR NVL72 Component BoM and Power Budget Model ↗
② Atomic Claim
因此,compute tray 中的 fans 被移除。
- Epistemic Mode:
ASSERTED - Mapping Status:
COMPLETE
③ Semantic Frame
{
"attribute": "FAN_REMOVAL",
"context_nodes": [],
"entity": {
"id": "04_knowledge_base/Compute Tray",
"label": "compute tray"
},
"frame_type": "ATTRIBUTE",
"qualifiers": {
"condition_text": "result of full liquid-cooling design context",
"numeric_mentions": [],
"temporal_mentions": []
},
"value": {
"numeric_mentions": [],
"value_text": "fans are removed from the compute tray."
}
}④ Canonical Entity Mapping
| Role | Surface Label | Canonical Target |
|---|---|---|
| entity | compute tray | 04_knowledge_base/Compute Tray |
⑤ V2 Draft(需要修正時直接編輯)
Inline repair
只編輯以下三個 Draft 區塊。完成後將
review_action設為REQUEST_REPAIR,再手動執行 Repair Preview。
執行腳本前,Draft 不會寫入 Claim Store 或 Graph。
V2 Atomic Claim Draft
因此,compute tray 中的 fans 被移除。
V2 Semantic Frame Draft
{
"attribute": "FAN_REMOVAL",
"context_nodes": [],
"entity": {
"id": "04_knowledge_base/Compute Tray",
"label": "compute tray"
},
"frame_type": "ATTRIBUTE",
"qualifiers": {
"condition_text": "result of full liquid-cooling design context",
"numeric_mentions": [],
"temporal_mentions": []
},
"value": {
"numeric_mentions": [],
"value_text": "fans are removed from the compute tray."
}
}V2 Revision Metadata Draft
{
"epistemic_mode": "ASSERTED",
"mapping_status": "COMPLETE"
}⑥ Human Review
請在 Properties 逐項確認:
- 原文 → Atomic Claim 是否忠實
- Atomic Claim → Semantic Frame 是否忠實
- Canonical Entity mapping 是否正確
- Epistemic mode 是否保留原文語氣
- 最後選擇
review_action
Review state
Markdown 內文不是正式 approval。只有 Apply bridge 寫入的 Decision Ledger event 才是正式決策。