GB200 Hardware Architecture - Component Supply Chain & BOM

Nvidia’s GB200 brings significant advances in performance via superior hardware architecture , but the deployment complexities rise dramatically. While on the face of it, Nvidia has released a standard rack that people will just install in their datacenters without much trouble, plug-and-play style, the reality is there are dozens of different deployment variants with tradeoffs and a significant complexity increase generation on generation. The supply chain gets reworked for end datacenter deployers, clouds, server OEMs / ODMs, and downstream component supply chains.

Nvidia 的 GB200 憑藉更優異的硬體架構,在效能上帶來顯著進步,但部署複雜度也大幅提升。表面上看,Nvidia 推出的是一套標準機櫃,似乎只要在資料中心直接安裝、以即插即用方式部署即可;但實際上存在數十種不同的部署變體,各自有不同取捨,而且相較前一世代,整體複雜度明顯增加。這也使終端資料中心部署商、雲端業者、伺服器 OEM/ODM,以及下游零組件供應鏈都必須重新調整。

Today we are going to go from A to Z on the different form factors of GB200 and how they changed versus the prior 8 GPU HGX baseboard servers. We will break downs on unit volumes, supplier market share and cost for over 50 different subcomponents of the GB200 rack. Furthermore, we will dive into the hyperscale customization that changes the subcomponent supply chain heavily. Lastly we will also do a deep dive into the various types of liquid cooling architectures, deployment complexities, and the supply chain there.

本文將從頭到尾介紹 GB200 的不同產品形態,以及相較前一代採用 8 顆 GPU 的 HGX 基板伺服器有哪些變化。我們會拆解 GB200 機櫃超過 50 種不同子零組件的出貨量、供應商市占率與成本。此外,也會深入分析 hyperscaler 客製化如何大幅改變子零組件供應鏈,最後再詳談各種液冷架構、部署複雜度與相關供應鏈。

Table of Contents:

GB200 form factors

GB200 產品形態

Power budget

Compute tray architecture

Compute tray 架構

Networking fabrics

NVLink fabric

NVL72

NVL36x2

NVL576

Backend fabric (Infiniband/Ethernet)

後端網路 fabric(InfiniBand/Ethernet)

Frontend fabric

Networking dollar content summary

網路設備金額含量摘要

Optics

DSP

Hyperscaler customization

Substrate, PCB, and CCL

基板、PCB 與 CCL

Liquid cooling

Rack architecture changes & content

機櫃架構變化與零組件含量

Heat transfer flow

熱傳導流程

L2A (Liquid to Air) vs L2L (Liquid to Liquid)

L2A(Liquid to Air,液體對空氣)與 L2L(Liquid to Liquid,液體對液體)比較

Redesigning data center infrastructure

重新設計資料中心基礎設施

Supply chain procurement decision maker & analysis

供應鏈採購決策者與分析

Liquid cooling components competition

液冷零組件競爭格局

Power delivery network, PDB, Busbar, VRM

電力傳輸網路、PDB、Busbar、VRM

BMC

Mechanical components

OEM / ODM Mapping

OEM/ODM 對應關係

The 4 Rack Scale Form Factors of Blackwell

With GB200 Racks, there are 4 different major form factors offered, with customization within each.

GB200 機櫃共有 4 種主要產品形態,而且每一種都還可以進一步客製化。

GB200 NVL72

GB200 NVL36x2

GB200 NVL36x2 (Ariel)

GB200 NVL36x2(Ariel)

x86 B200 NVL72/NVL36x2

x86 B200 NVL72/NVL36x2

The first one is the GB200 NVL72 form factor. This form factor requires approximately 120kW per rack. To put this density into context, a general-purpose CPU rack supports up to 12kW/rack, while the higher-density H100 air-cooled racks typically only support about 40kW/rack. Moving well past 40kW per rack is the primary reason why liquid cooling is required for GB200.

第一種是 GB200 NVL72。這種產品形態每櫃約需要 120kW。作為密度比較,一般用途 CPU 機櫃最高約支援 12kW/rack,而較高密度、採氣冷的 H100 機櫃通常也只支援約 40kW/rack。當單櫃功率密度大幅超過 40kW 時,也就成為 GB200 必須採用液冷的主要原因。

Atomic Claim 1/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0001

Claim: GB200 NVL72 每個 rack 約需 120kW。
Frame: ATTRIBUTE · Mode: ESTIMATED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 2/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0002

Claim: GB200 因 rack 功率密度超過約 40kW 而需要 liquid cooling
Frame: RELATION · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

image

Source: SemiAnalysis

The GB200 NVL72 racks consists of 18 1U compute trays and 9 NVSwitch trays. Each compute tray is 1U in height and contains 2 Bianca boards. Each Bianca board is 1 Grace CPU and 2 Blackwell GPUs. The NVSwitch trays have two 28.8Tb/s NVSwitch5 ASICs.

GB200 NVL72 機櫃由 18 個 1U compute tray 與 9 個 NVSwitch tray 組成。每個 compute tray 高度為 1U,內含 2 張 Bianca board;每張 Bianca board 配置 1 顆 Grace CPU 與 2 顆 Blackwell GPU。每個 NVSwitch tray 則配置 2 顆 28.8Tb/s 的 NVSwitch5 ASIC。

Atomic Claim 3/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0003

Claim: GB200 NVL72 rack 由 18 個 1U compute trays 與 9 個 NVSwitch trays 組成。
Frame: NARY_RELATION · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 4/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0004

Claim: compute tray 高度為 1U,並包含 2 個 Bianca boards
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 5/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0005

Claim: 每個 NVSwitch tray 配有 2 顆 28.8Tb/s NVSwitch5 ASICs
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: PARTIAL
開啟逐條審核

With the exception of one hyperscaler who plans to deploy this as the primary variant, we believe that this version will be rarely deployed until Blackwell Ultra as most datacenter infrastructure cannot support this high of a rack density even with direct-to-chip liquid cooling (DLC).

除了有一家 hyperscaler 計畫把這個版本作為主要部署方案之外,我們認為在 Blackwell Ultra 之前,這個版本的實際部署量都會很少,因為即使採用 direct-to-chip liquid cooling(DLC),多數資料中心基礎設施仍無法支援如此高的單櫃功率密度。

The next form factor is the GB200 NVL36 * 2 which is two racks side by side interconnected together. Most of the GB200 racks will use this form factor. Each rack contains 18 Grace CPUs and 36 Blackwell GPUs. Between the 2 racks, it still maintains being non-blocking all-to-all between all the 72 GPUs found in NVL72. Each compute tray is 2U in height and contains 2 Bianca boards. Each NVSwitch tray has two 28.8Tb/s NVSwitch5 ASIC chips. Each chip has 14.4Tb/s pointing backward toward the backplane and 14.4Tb/s pointing toward the front plate. Each NVswitch tray has 18 1.6T twin-port OSFP cages which connect horizontally to a pair NVL36 rack.

下一種產品形態是 GB200 NVL36 × 2,也就是兩個並排且彼此互連的機櫃。我們認為大多數 GB200 機櫃都會採用這種形式。每個機櫃配置 18 顆 Grace CPU 與 36 顆 Blackwell GPU;兩個機櫃合計 72 顆 GPU,仍可維持與 NVL72 相同的 non-blocking all-to-all 互連。每個 compute tray 高 2U,內含 2 張 Bianca board。每個 NVSwitch tray 有 2 顆 28.8Tb/s NVSwitch5 ASIC;每顆晶片有 14.4Tb/s 朝向後方 backplane,另有 14.4Tb/s 朝向前面板。每個 NVSwitch tray 還有 18 個 1.6T 雙埠 OSFP cage,用來水平連接一對 NVL36 機櫃。

Atomic Claim 6/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0006

Claim: 每個 NVL36 rack 包含 18 顆 Grace CPUs 與 36 顆 Blackwell GPUs。
Frame: NARY_RELATION · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 7/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0007

Claim: GB200 NVL36x2 的兩個 rack 之間維持 72 顆 GPU 的 non-blocking all-to-all 連線。
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: PARTIAL
開啟逐條審核

Atomic Claim 8/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0008

Claim: 在 GB200 NVL36x2 中,每個 compute tray 高度為 2U,並包含 2 個 Bianca boards
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 9/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0009

Claim: GB200 NVL36x2 的 NVSwitch5 ASIC 每顆有 14.4Tb/s 朝向 backplane,另有 14.4Tb/s 朝向前面板。
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: PARTIAL
開啟逐條審核

Atomic Claim 10/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0010

Claim: 每個 NVSwitch tray 有 18 個 1.6T twin-port OSFP cages,用於橫向連接一對 NVL36 racks。
Frame: NARY_RELATION · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

image

Source: SemiAnalysis

The per rack power & cooling density is 66kW per rack for a total of 132kW for NVL36 racks * 2. This is the time to market solution as each rack is only 66kW/rack. Unfortunately, a NVL36x2 system does use ~10kW more power compared to NVL72 due to the additional NVSwitch ASICs and the requirement for cross rack interconnect cabling. NVL36x2 will have 36 NVSwitch5 ASICs in total compared to only 18 NVSwitch5 ASICs on the NVL72. Even with this increase in overall power of 10kW, most firms will deploy this version next year instead of NVL72 as their datacenter can’t support 120kW per rack density. We will discuss the reason for this later in the liquid cooling section.

NVL36 × 2 每個機櫃的功耗與散熱密度為 66kW,兩櫃合計 132kW。因為單櫃只有 66kW/rack,這是較有利於快速上市的解決方案。不過 NVL36x2 因為增加了 NVSwitch ASIC,以及需要跨機櫃互連線纜,整套系統功耗會比 NVL72 高約 10kW。NVL36x2 總共有 36 顆 NVSwitch5 ASIC,而 NVL72 只有 18 顆。即使整體功耗多了約 10kW,我們仍認為多數業者明年會選擇 NVL36x2 而不是 NVL72,因為它們的資料中心無法支援 120kW/rack 的密度。後面的液冷章節會再說明原因。

Atomic Claim 11/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0011

Claim: NVL36 每 rack 的 power/cooling density 為 66kW,兩個 rack 合計 132kW。
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

The last form factor is the specific rack with a custom “Ariel” board instead of the standard Bianca. We believe this variant will primarily be used by Meta. Due to Meta’s recommendation system training and inferencing workloads, they require a higher CPU core and more memory per GPU ratio in order to store massive embedding tables and perform pre/post-processing on the CPUs.

最後一種產品形態是採用客製化「Ariel」板、取代標準 Bianca 的特定機櫃。我們認為這個版本主要會由 Meta 使用。由於 Meta 的推薦系統訓練與推論工作負載,需要儲存龐大的 embedding table,並在 CPU 上進行前處理與後處理,因此每顆 GPU 所需的 CPU core 數量與記憶體配置都更高。

The content is similar to the standard GB200 NVL72: but instead the Bianca board is swapped for an Ariel board that has 1 Grace CPU and 1 Blackwell GPU. Due to the doubling of Grace CPU content per GPU, this SKU will be more expensive even compared to NVL36x2. Similar to NVL36x2, each NVSwitch tray has 18 1.6T twin-port OSFP cages which connect horizontally to a pair NVL36 rack.

其整體配置與標準 GB200 NVL72 類似,但 Bianca board 會改成 Ariel board,每張 Ariel board 配置 1 顆 Grace CPU 與 1 顆 Blackwell GPU。由於每顆 GPU 所搭配的 Grace CPU 數量增加一倍,這個 SKU 即使與 NVL36x2 相比也會更昂貴。與 NVL36x2 類似,每個 NVSwitch tray 都有 18 個 1.6T 雙埠 OSFP cage,用來水平連接一對 NVL36 機櫃。

image

Source: SemiAnalysis

We believe that the majority of Meta’s allocation will be the normal NVL36x2 as that is more geared towards GenAI workloads while the Ariel version will just be for their largest Recommendation System workloads . While there is nothing preventing Ariel from being used for GenAI workloads, the overprovisioning of CPUs means it will be inferior from a TCO standpoint due to higher capital cost and power.

我們認為 Meta 大部分的配額仍會採用一般 NVL36x2,因為這種配置更適合 GenAI 工作負載;Ariel 版本則主要用於其最大型的 Recommendation System 工作負載。雖然 Ariel 並非不能用於 GenAI,但 CPU 配置過度供給,會帶來較高的資本成本與耗電,因此從 TCO 角度來看較不具優勢。

Lastly, in Q2 2025, there will be a B200 NVL72 and NVL36x2 form factor that will use x86 CPUs instead of Nvidia’s in-house grace CPU. This form factor is called Miranda. We believe that the CPU to GPU per compute tray will stay the same at 2 CPUs and 4 GPUs per compute tray.

最後,在 2025 年第二季,還會推出使用 x86 CPU、而非 Nvidia 自研 Grace CPU 的 B200 NVL72 與 NVL36x2 產品形態,這個版本稱為 Miranda。我們認為每個 compute tray 的 CPU 對 GPU 配置會維持不變,仍是 2 顆 CPU 搭配 4 顆 GPU。

We believe that this variant of NVL72/NVL36x2 will have lower upfront capital cost compared to the Grace CPU version, with less revenue flowing to Nvidia. Since it is using an x86 CPU, there will be much lower CPU to GPU bandwidth compared to Grace C2C which can talk to the GPUs at up to 900GB/s bidirectional (450GB/s). Because of this TCO is questionable. Furthermore as the x86 CPUs will not be able to share power between the CPU and GPUs to optimize for the workload total peak power required is much higher. In our accelerator model, we have broken down which GB200 form factors & the exact volume each of the top 50 buyers will be deploying.

我們認為這個 NVL72/NVL36x2 版本相較 Grace CPU 版本,前期資本支出會較低,流向 Nvidia 的營收也會較少。由於採用 x86 CPU,CPU 與 GPU 之間的頻寬會遠低於 Grace C2C;Grace C2C 與 GPU 的雙向頻寬最高可達 900GB/s(單向 450GB/s),因此這個版本的 TCO 是否具優勢仍有疑問。此外,x86 CPU 無法在 CPU 與 GPU 之間共享功率、依工作負載動態最佳化,因此整體所需峰值功率會高得多。我們在 accelerator model 中已拆解前 50 大買家分別會部署哪些 GB200 產品形態,以及各自的精確數量。

Power Budget Estimates

We estimate that the max TDP of each compute tray is 6.3kW. Most of the power draw from the compute tray is from the two Bianca board and 8 fans in each tray. The NVSwitch tray in NVL72 does not need to connect between racks as such has a 170W lower power draw compared to NVL36. With NVL36, there are 18 1.6T ACC cables to connect horizontally to the neighboring rack. We will explain the NVLink topology in further sections. 123.6kW per NVL72 is the total power draw including the inefficiencies from rectifying from AC power from the whip to DC power that the compute tray takes in.

我們估計每個 compute tray 的最大 TDP 為 6.3kW。compute tray 的主要耗電來自兩張 Bianca board,以及每個 tray 內的 8 顆風扇。NVL72 的 NVSwitch tray 不需要跨機櫃連接,因此相較 NVL36 功耗低 170W。NVL36 則需要 18 條 1.6T ACC 線纜,水平連接相鄰機櫃;後文會進一步解釋 NVLink 拓樸。每套 NVL72 的總功耗為 123.6kW,這已包含從機櫃電源 whip 的 AC 電力整流成 compute tray 所使用 DC 電力時產生的效率損失。

Atomic Claim 12/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0012

Claim: SemiAnalysis 估計每個 compute tray 的最大 TDP 為 6.3kW。
Frame: ATTRIBUTE · Mode: ESTIMATED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 13/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0013

Claim: compute tray 的主要功耗來自 2 個 Bianca boards 與每 tray 8 個 fans。
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 14/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0014

Claim: NVL72 的 NVSwitch tray 因不需跨 rack 連接,功耗比 NVL36 低 170W。
Frame: COMPARISON · Mode: ASSERTED · Mapping: PARTIAL
開啟逐條審核

Atomic Claim 15/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0015

Claim: NVL36 使用 18 條 1.6T ACC cables 橫向連接相鄰 rack。
Frame: RELATION · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 16/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0016

Claim: NVL72 的總功耗為 123.6kW,包含 AC 轉 DC 的整流損耗。
Frame: ATTRIBUTE · Mode: ESTIMATED · Mapping: PARTIAL
開啟逐條審核

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

While for NVL36*2, each rack has a max TDP of ~67kW while both rack pairs take in ~132kW. This is approximately 10kW more power draw compared to NVL72.

至於 NVL36 × 2,每個機櫃的最大 TDP 約為 67kW,兩個機櫃合計約 132kW,比 NVL72 約多出 10kW 的功耗。

Atomic Claim 17/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0017

Claim: NVL36x2 每個 rack 的最大 TDP 約 67kW,兩 rack 合計約 132kW。
Frame: ATTRIBUTE · Mode: ESTIMATED · Mapping: COMPLETE
開啟逐條審核

Compute Tray Diagrams & Cabling

The heart of the GB200 NVL72/NVL36x2 is the Bianca board. The Bianca board contains two Blackwell B200 GPUs and a single Grace CPU. The ratio between CPU and GPU is now 1:2 on a board compared to GH200, which is a 1:1 ratio. Most of the customers that evaluated GH200 have told Nvidia that it was too expensive as 1:1 CPU ratio was too much for their workloads. This is one of the main reasons why GH200 shipped in such low volumes compared to HGX H100 (2 x86 CPUs, 8 H100 GPUs). For Blackwell, GB200 volume is way up relatively and there will be crossover in unit shipments versus HGX Blackwell B100/B200.

GB200 NVL72/NVL36x2 的核心是 Bianca board。每張 Bianca board 配置 2 顆 Blackwell B200 GPU 與 1 顆 Grace CPU,因此板上 CPU:GPU 比例為 1:2;相比之下,GH200 是 1:1。多數曾評估 GH200 的客戶都向 Nvidia 反映,1:1 的 CPU 配置對其工作負載而言過於昂貴,這也是 GH200 相較 HGX H100(2 顆 x86 CPU、8 顆 H100 GPU)出貨量偏低的主要原因之一。到了 Blackwell 世代,GB200 的相對出貨量大幅增加,單位出貨量將會超越 HGX Blackwell B100/B200。

Atomic Claim 18/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0018

Claim: Bianca board 包含 2 顆 B200 GPUs 與 1 顆 Grace CPU
Frame: NARY_RELATION · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 19/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0019

Claim: Bianca board 的 CPU:GPU 比例為 1:2,相較之下 GH200 為 1:1。
Frame: COMPARISON · Mode: ASSERTED · Mapping: PARTIAL
開啟逐條審核

image

Source: SemiAnalysis

Normally in Hopper & Blackwell HGX servers, there are Broadcom PCIe switches between the CPU and the GPU. For the GB200, the CPU and GPU are both on the same PCB, reducing insertion loss to a point that there is no longer any need for switches or retimers between the CPU and GPU on the reference design. This is on the surface is extremely negative for Astera Labs. It now has ~35% short interest of free float, but that mostly from folks who aren’t following the supply chain deeply and only understand there are no retimers in the reference design. We will share more details below and in the GB200 Component & Supply Chain Model .

一般 Hopper 與 Blackwell HGX 伺服器中,CPU 與 GPU 之間會配置 Broadcom PCIe switch。GB200 則把 CPU 與 GPU 放在同一張 PCB 上,使 insertion loss 降低到 reference design 不再需要 CPU 與 GPU 之間的 switch 或 retimer。表面上看,這對 Astera Labs 極為不利。其目前約有自由流通股 35% 的放空比率,但我們認為這主要來自沒有深入追蹤供應鏈、只知道 reference design 沒有 retimer 的投資人。後文以及 GB200 Component & Supply Chain Model 會提供更多細節。

Atomic Claim 20/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0020

Claim:GB200 reference design 中,CPUGPU 位於同一張 PCB,降低 insertion loss,因此 CPU 與 GPU 間不再需要 switches 或 retimers。
Frame: NARY_RELATION · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

Another interesting thing about the reference design is that instead of using the typical MCIO PCIe x16 connectors to connect the main PCB board to a PCIe form factor ConnectX-7/8, the ConnectX-7/8 ICs now sit directly on top of the Bianca board using a mezzanine board via Mirror Mezz connectors.

reference design 另一個值得注意的地方是,不再使用典型的 MCIO PCIe x16 連接器,把主 PCB 連到 PCIe form factor 的 ConnectX-7/8;現在 ConnectX-7/8 IC 會透過 Mirror Mezz connector 與 mezzanine board,直接安裝在 Bianca board 上方。

image

Source: SemiAnalysis

This has the advantage of using the same cold plate to cool both the CPUs, GPUs, and ConnectX-7/8 NICs. The electrical lanes are routed to the OSFP cages at the front of the chassis with DensiLink connectors from the mezzanine board. This is similar to how Nvidia used DensiLink on their gold plated DGX H100 chassis to route from the ConnectX-7 to the OSFP cages.

這樣的優點是 CPU、GPU 與 ConnectX-7/8 NIC 都可以共用同一塊 cold plate 散熱。電氣訊號會從 mezzanine board 經由 DensiLink connector,連到機箱前方的 OSFP cage。這與 Nvidia 在鍍金版 DGX H100 機箱上的做法類似,當時也是使用 DensiLink,把 ConnectX-7 訊號連到 OSFP cage。

Atomic Claim 21/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0021

Claim: GB200 reference design 使用同一個 cold plate 同時冷卻 CPUGPUConnectX-7/8 NIC。
Frame: NARY_RELATION · Mode: ASSERTED · Mapping: PARTIAL
開啟逐條審核

Similar to the Dual GH200, within the same compute tray, there is a high speed Coherent NVLink connection that operates up to 600GB/s bidirectional bandwidth (300GB/s unidirectional). This is an extremely fast connection and allows the CPUs to share resources and memory similar to the HGX H100/B100/B200 servers which have 2 CPUs and have NUMA (Non-Uniform Memory Access) regions.

與 Dual GH200 類似,同一個 compute tray 內設有高速 Coherent NVLink 連線,雙向頻寬最高可達 600GB/s(單向 300GB/s)。這是一條非常高速的連線,使 CPU 能共享資源與記憶體,效果類似 HGX H100/B100/B200 伺服器;後者配置 2 顆 CPU,並具有 NUMA(Non-Uniform Memory Access)區域。

Atomic Claim 22/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0022

Claim: 同一個 compute tray 內的 coherent NVLink 連線最高提供 600GB/s 雙向頻寬(300GB/s 單向)。
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

image

Source: Nvidia

Due to this coherent link that hooks up two Bianca board, you can share memory, storage & resources such as NICs between the CPUs. For this reason, you will be able to depopulate a frontend NICs and only have 1 frontend NIC per compute tray instead of 2 as suggested in the reference design. This is similar to how in x86, even though, you have 2 CPUs per server, you only need 1 frontend NIC since the CPUs are able to share resources. We will discuss this more in the frontend networking section.

由於這條 coherent link 會把兩張 Bianca board 連接起來,因此 CPU 之間可以共享記憶體、儲存裝置與 NIC 等資源。基於這個原因,可以減少 frontend NIC 的配置,每個 compute tray 只保留 1 張 frontend NIC,而不是 reference design 建議的 2 張。這與 x86 伺服器類似:即使每台伺服器有 2 顆 CPU,由於 CPU 能共享資源,因此只需要 1 張 frontend NIC。後面的 frontend networking 章節會再進一步說明。

image

Source: SemiAnalysis

In terms of how the 2700 Watts of power gets to the board, there are 4 RapidLock 12V DC and 4 RapidLock GND (Ground) Power Connectors located around the CPU and GPU’s respective voltage regulator modules (VRM). These 12V and GND power connectors will connect to the compute tray’s power distribution board (PDB). The power distribution board takes 48V DC from the rack level busbar and steps it down to 12V DC for the Bianca board. We will discuss the changes to the power delivery network for the system in the power delivery section later.

至於 2700W 的電力如何送到板上,在 CPU 與 GPU 各自的 voltage regulator module(VRM)周圍,配置了 4 個 RapidLock 12V DC 與 4 個 RapidLock GND(接地)電源連接器。這些 12V 與 GND 連接器會接到 compute tray 的 power distribution board(PDB)。PDB 從機櫃層級 busbar 接收 48V DC,再降壓至 12V DC 供 Bianca board 使用。後面的電力傳輸章節會再說明整套系統 power delivery network 的變化。

image

Source: SemiAnalysis

In terms of the internal compute tray cables + connectors, most of the cost is dominated by the Mirror mezz connectors that connect the ConnectX-7/8 mezzanine board to the Bianca board & by the DensiLink cables that connect from the ConnectX-7/8 to the OSFP cages on the front of the chassis.

在 compute tray 內部線纜與連接器的成本中,最大宗主要是把 ConnectX-7/8 mezzanine board 連到 Bianca board 的 Mirror Mezz connector,以及把 ConnectX-7/8 連到機箱前方 OSFP cage 的 DensiLink 線纜。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

In the Nvidia reference design, there are two Bluefield-3s per compute tray, but as explained in later sections, we believe that most firms will not opt for any Bluefield-3 at all. At the front of the chassis, you can find all your typical server-related management ports, like RJ45, USB, etc. There are also eight NVMe storage bays for local node-level storage, and you can also find your scale-out backend OSFP cages.

在 Nvidia reference design 中,每個 compute tray 配置 2 顆 BlueField-3;但如後文所述,我們認為多數業者最後一顆 BlueField-3 都不會選配。機箱前方可以看到一般伺服器常見的管理連接埠,例如 RJ45、USB 等;另外還有 8 個 NVMe 儲存槽供節點本地儲存使用,以及 scale-out backend 的 OSFP cage。

image

Source: SemiAnalysis

The backend cage leads us to discuss one of the most critical pieces of the GB200: networking.

談到 backend cage,就帶到 GB200 最關鍵的部分之一:網路。

Networking

Similar to the HGX H100, AMD MI300X, Intel Gaudi, AWS Trainium, there are 4 different networks in the GB200 systems:

與 HGX H100、AMD MI300X、Intel Gaudi、AWS Trainium 類似,GB200 系統中也有 4 種不同的網路:

Frontend Networking (Normal Ethernet)

前端網路(一般 Ethernet)

Backend Networking (InfiniBand/RoCE Ethernet)

後端網路(InfiniBand/RoCE Ethernet)

Accelerator Interconnect (NVLink)

加速器互連(NVLink)

Out of Band Networking

Out-of-Band 管理網路

As a quick refresher, the frontend networking is just your normal ethernet network that you use to connect to the internet, SLURM/Kubernetes, networked storage, data loading, model checkpoints. This network is typically 25-50Gb/s per GPU, so on a HGX H100 server, it will be 200-400Gb/s per server, while on a GB200 computer tray node, it will be 200-800Gb/s per server depending on the configuration.

簡單複習一下,frontend networking 就是一般 Ethernet 網路,用於連接網際網路、SLURM/Kubernetes、網路儲存、資料載入與 model checkpoint。這類網路通常每顆 GPU 為 25–50Gb/s,因此 HGX H100 伺服器每台約為 200–400Gb/s,而 GB200 compute tray node 則依配置不同,每台約為 200–800Gb/s。

Atomic Claim 23/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0023

Claim: GB200 compute tray node 的 frontend networking 依配置約為 200–800Gb/s per server。
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

Your backend network is used to scale out GPU-GPU communications across hundred to thousands of racks. This network could either be Nvidia’s Infiniband or Nvidia Spectrum-X Ethernet or Broadcom Ethernet. With the options from Nvidia being way more expensive compared to the Broadcom Ethernet solutions .

backend network 用來把 GPU-to-GPU 通訊 scale out 到數百甚至數千個機櫃。這個網路可以採用 Nvidia InfiniBand、Nvidia Spectrum-X Ethernet,或 Broadcom Ethernet;其中 Nvidia 的方案價格遠高於 Broadcom Ethernet 解決方案。

Atomic Claim 24/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0024

Claim: GB200 類系統的 backend network 用於跨數百至數千個 racks 的 GPU-to-GPU scale-out,選項包括 Nvidia InfiniBand、Spectrum-X Ethernet 或 Broadcom Ethernet。
Frame: NARY_RELATION · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

The scale-up accelerator interconnect (NVLink on Nvidia , Infinity Fabric/UALink on AMD, ICI on Google TPU , NeuronLink on Amazon Trainium 2) is an ultra-high speed network that connects GPUs together within a system. On Hopper, this network connected 8 GPUs together at 450GB/s each while on Blackwell NVL72, it will connect 72 GPUs together at 900GB/ each. There is a variant of Blackwell called NVL576 that will connect 576 GPUs together but basically no customers will opt for it. In general, your accelerator interconnect is 8-10x faster than your backend networking.

scale-up accelerator interconnect(Nvidia 為 NVLink、AMD 為 Infinity Fabric/UALink、Google TPU 為 ICI、Amazon Trainium 2 為 NeuronLink)是一種在系統內部連接 GPU 的超高速網路。Hopper 世代可把 8 顆 GPU 互連,每顆頻寬為 450GB/s;到了 Blackwell NVL72,則可把 72 顆 GPU 互連,每顆頻寬達 900GB/s。Blackwell 另外還有 NVL576 版本,可連接 576 顆 GPU,但基本上沒有客戶會選用。整體而言,accelerator interconnect 的速度通常比 backend networking 快 8–10 倍。

Atomic Claim 25/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0025

Claim: Blackwell NVL72 的 scale-up accelerator interconnect 連接 72 顆 GPU、每顆約 900GB/s;Hopper 則是 8 顆 GPU、每顆 450GB/s。
Frame: COMPARISON · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 26/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0026

Claim: Accelerator scale-up interconnect 一般約比 backend networking 快 8–10 倍。
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: PARTIAL
開啟逐條審核

Lastly, there is your out of band management network which is used for re-imaging your operating system, monitor node health such as fan speed, temperatures, power draw, etc. Your baseboard management controller (BMC) on servers, PDUs, switches, CDUs are usually connected to this network to monitor and control these IT equipment.

最後還有 out-of-band management network,用於重新安裝作業系統映像,以及監控風扇轉速、溫度、功耗等節點健康狀態。伺服器、PDU、switch、CDU 上的 baseboard management controller(BMC)通常都會連到這個網路,以監控並控制這些 IT 設備。

Compared to HGX H100, the frontend, backend and out of band networking of GB200 are mostly same with the exception of NVLink expanding outside of the chassis. Only hyperscaler customizations are different gen on gen. Previously in HGX H100, the 8 GPUs and 4 NVSwitch4 Switch ASICs are connected together using PCB traces as they are on the same PCB, the HGX baseboard.

相較 HGX H100,GB200 的 frontend、backend 與 out-of-band networking 大致相同,主要差異在於 NVLink 延伸到機箱之外;真正世代間不同的主要是 hyperscaler 客製化。過去在 HGX H100 中,8 顆 GPU 與 4 顆 NVSwitch4 switch ASIC 位於同一張 HGX baseboard 上,因此彼此透過 PCB trace 連接。

image

Source: SemiAnalysis

Now on HGX Blackwell, the NVSwitch ASICs are in the middle to reduce the length of the PCB trace given the upgraded 224G SerDes

到了 HGX Blackwell,因 SerDes 升級至 224G,NVSwitch ASIC 被放到中間位置,以縮短 PCB trace 長度。

But on the GB200, the NVSwitches are on a different tray from GPUs and therefore you need to either use Optics or ACCs to connect between them.

但在 GB200 上,NVSwitch 與 GPU 位於不同 tray,因此兩者之間必須使用光學連線或 ACC 連接。

Atomic Claim 27/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0027

Claim: GB200 的 NVSwitch 與 GPU 位於不同 tray,因此兩者之間需要 optics 或 ACC 連接。
Frame: NARY_RELATION · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

image

Source: Nvidia

In NVL72, they keep the same flat 1 tier NVLink topology as HGX Hopper/Blackwell such that you can talk to any of the GPUs within the same rack with only 1 hop through an NVSwitch. This is unlike AMD & Intel’s current generation interconnect which connects directly from GPU to GPU without a switch, which leads to reduced Accelerator to Accelerator bandwidth.

NVL72 維持與 HGX Hopper/Blackwell 相同的單層扁平 NVLink 拓樸,因此同一機櫃內任兩顆 GPU 之間,只需要經過 1 次 NVSwitch hop 就能通訊。這不同於 AMD 與 Intel 現世代的互連方式;後者採 GPU 直接連 GPU、沒有 switch,因此 accelerator-to-accelerator 頻寬較低。

Atomic Claim 28/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0028

Claim: NVL72 採 flat 1-tier NVLink topology,同 rack 任一 GPU 之間僅需經過 1 個 NVSwitch hop。
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

image

Source: SemiAnalysis

In NVL36x2, it only takes 1 hop to get to any of the 36 GPUs within the same rack but in order to talk to the other 36 GPUs in the rack beside it, it takes 2 NVSwitch hops to get across the racks. Intuitively, one additional hop adds latency but is not noticeable for training. It will slightly impact inference, but not too much unless extremely high interactivity (>500TPS) at batch 1 without speculative decoding is the target. Note that is quite an unrealistic scenario we don’t expect anyone to utilize.

在 NVL36x2 中,同一個機櫃內任一顆 GPU 要連到其餘 35 顆 GPU 都只需 1 hop;但若要與旁邊另一個機櫃中的 36 顆 GPU 通訊,則需要經過 2 次 NVSwitch hop 才能跨櫃。直覺上多一個 hop 會增加 latency,但對訓練幾乎沒有明顯影響。推論會受到些微影響,但除非目標是在 batch 1、沒有 speculative decoding 的情況下追求極高互動性(>500 TPS),否則影響不大;我們認為這種情境相當不實際,幾乎不會有人採用。

Atomic Claim 29/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0029

Claim: NVL36x2 中,同 rack 的 36 顆 GPU 需 1 hop;跨到相鄰 rack 的另 36 顆 GPU 則需 2 個 NVSwitch hops。
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

image

Source: SemiAnalysis

Nvidia claims that if they used optics with transceivers, they would have needed to add 20kW per NVL72 rack. We did the math and calculated that it would need to use 648 1.6T twin port transceivers with each transceiver consuming approximately 30Watts so the math works out to be 19.4kW/rack which is basically the same as Nvidia’s claim. At about 550,800 per rack in just transceiver costs alone. When you mark that up by Nvidia’s 75% gross margin, that would mean $2,203,200 per rack of NVLink transceivers that the end customer would need to pay. This is one of the main reasons why DGX H100 NVL256 never shipped due to the massive cost of transceivers. Furthermore, bleeding edge transceivers like the 1.6T NVLink transceivers have way worse reliability compared to copper cables or even prior generation optics.

Nvidia 表示,如果改用帶 transceiver 的光學方案,每個 NVL72 機櫃會額外增加約 20kW 功耗。我們自行計算後發現,需要 648 個 1.6T 雙埠 transceiver,每個約消耗 30W,因此總功耗約為 19.4kW/rack,與 Nvidia 的說法幾乎一致。若每個 1.6T transceiver 約 850 美元,單是 transceiver 成本每櫃就達 550,800 美元;再按照 Nvidia 75% 毛利率加價,終端客戶每個 NVL72 機櫃需支付的 NVLink transceiver 金額將達 2,203,200 美元。這是 DGX H100 NVL256 最終沒有出貨的主要原因之一,因為 transceiver 成本過高。此外,1.6T NVLink transceiver 這類最先進光收發模組的可靠度,也遠差於銅纜,甚至比前一代光學方案更差。

Atomic Claim 30/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0030

Claim: Nvidia 聲稱若 NVL72 使用 optical transceivers,將增加約 20kW/rack 的功耗。
Frame: ATTRIBUTE · Mode: ATTRIBUTED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 31/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0031

Claim: SemiAnalysis 計算 NVL72 若採 optics,需 648 個 1.6T twin-port transceivers、每個約 30W,合計約 19.4kW/rack。
Frame: ATTRIBUTE · Mode: ESTIMATED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 32/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0032

Claim: 以每個 1.6T transceiver 約 850 美元估算,NVL72 單 rack transceiver 成本約 550,800 美元。
Frame: ATTRIBUTE · Mode: ESTIMATED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 33/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0033

Claim: SemiAnalysis 以 Nvidia 75% gross margin 推算,NVL72 的 NVLink transceivers 終端價格約 2.2032 百萬美元/rack。
Frame: ATTRIBUTE · Mode: ESTIMATED · Mapping: COMPLETE
開啟逐條審核

As such, this is the reason Nvidia chose to use 5184 copper cables, which is a much cheaper, less power hungry, and more reliable option. Each GPU has 900GB/s unidirectional bandwidth. Each differential pair (DP) is capable of transmitting 200Gb/s in 1 direction thus it will take 72 DP per GPU for both directions. Since there are 72 GPUs per NVL72 rack, that would mean there is 5184 differential pairs. Each NVLink cable contains 1 differential pair thus there are 5184 cables.

因此 Nvidia 選擇使用 5,184 條銅纜,因為成本更低、耗電更少,而且可靠度更高。每顆 GPU 的單向頻寬為 900GB/s;每一組 differential pair(DP)單方向可傳輸 200Gb/s,因此若計入雙向傳輸,每顆 GPU 需要 72 組 DP。NVL72 每櫃有 72 顆 GPU,因此總共需要 5,184 組 differential pair。每條 NVLink cable 只包含 1 組 differential pair,所以總線纜數為 5,184 條。

Atomic Claim 34/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0034

Claim: Nvidia 在 NVL72 選擇使用 5,184 條 copper cables,以降低成本、功耗並提高可靠性。
Frame: NARY_RELATION · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 35/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0035

Claim: NVL72 每顆 GPU 為 900GB/s 單向頻寬,每 differential pair 為 200Gb/s 單向;雙向每 GPU 需 72 DP,72 顆 GPU 合計 5,184 DPs。
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

This is a massive increase in copper content generation on generation. In a bit of a whiplash, we have seen some investors estimate that there is around 216k/NVL72 rack but this is completely wrong.

這代表相較前一世代,銅材含量大幅增加。我們也看到一些投資人據此估計,每顆 GPU 的 NVLink 互連價值量約 3,000 美元,推算每個 NVL72 機櫃總額達 216,000 美元,但這個估算完全錯誤。

image

Source: Coatue

First of all, how did people even get to ridiculous numbers such as 162. Since it takes 18 400Gb/s full duplex cables per GPU, that would bring the price per GPU to $3k. This figure is wrong by a massive margin.

首先,市場到底是怎麼算出每顆 GPU 3,000 美元這種誇張數字?我們認為有人把每顆 GPU 單向 900GB/s(7,200Gb/s)的頻寬,拿去對照一條 400Gb/s 銅纜 162 美元的零售價。由於每顆 GPU 需要 18 條 400Gb/s full-duplex 線纜,於是就算出每顆 GPU 約 3,000 美元,但這個數字的誤差非常大。

image

Source: SemiAnalysis

Furthermore, there is a misconception that the cables are expensive. Most of the cost is not from the cables itself but instead in termination of the cables & the connectors. The connectors are expensive as they need to prevent crosstalk between different differential pairs. Crosstalk is extremely bad as it blurs out other signals and causes errors where the de-serializers can’t read the correct bits. Nvidia has chosen to use the Ultrapass Paladin backplane product from Amphenol for their NVLink backplane interconnect as the primary initial source.

此外,另一個誤解是認為線纜本身很昂貴。實際上大部分成本並不在線纜,而是在端接與連接器。連接器成本高,是因為必須抑制不同 differential pair 之間的 crosstalk。串音會嚴重干擾其他訊號、造成波形模糊,進而讓 de-serializer 無法正確辨識 bit 而產生錯誤。Nvidia 的 NVLink backplane interconnect 初期主要採用 Amphenol 的 Ultrapass Paladin backplane 產品。

Atomic Claim 36/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0036

Claim: Nvidia 的 NVLink backplane 初期主要採用 Amphenol Ultrapass Paladin backplane。
Frame: NARY_RELATION · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

We will use the primary source’s name for each connector and cable in the article, but the there are 3 sources with varying share over time, details of which we share in the full GB200 Component & Supply Chain Model

本文在提到各種連接器與線纜時,會使用主要供應商的產品名稱;實際上共有 3 家供應來源,而且市占會隨時間變化,詳細資訊整理在完整的 GB200 Component & Supply Chain Model 中。

image

Source: SemiAnalysis

Each Blackwell GPU is connected to an Amphenol Paladin HD 224G/s connector, each with 72 differential pairs. Then, that connector attaches to the backplane Paladin connector. Next, it will connect using SkewClear EXD Gen 2 Cable to the NVSwitch tray Paladin HD connector with 144 differential pairs per connector. From the NVSwitch Paladin connector to the NVSwitch ASIC chip, OverPass flyover cables are needed since there are 4 144 DP connectors (576 DPs) per switch tray and there would be way too much crosstalk to do PCB traces in such a small area. Furthermore loss over the PCB is worse than over the flyover cables.

每顆 Blackwell GPU 都連到一個 Amphenol Paladin HD 224G/s 連接器,每個連接器含 72 組 differential pair;接著再接到 backplane 上的 Paladin connector,之後透過 SkewClear EXD Gen 2 cable 連至 NVSwitch tray 的 Paladin HD connector,而每個 NVSwitch 端連接器含 144 組 differential pair。從 NVSwitch Paladin connector 到 NVSwitch ASIC 晶片之間則需要 OverPass flyover cable,因為每個 switch tray 上有 4 個、各 144 DP 的連接器,總計 576 DP;若在這麼小的面積內全部使用 PCB trace,crosstalk 會過於嚴重,而且 PCB 上的訊號損耗也比 flyover cable 更差。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

With NVL36x2, each system will require an additional 162 1.6T twin-port horizontal ACC cables which are extremely pricey to connect the NVSwitch trays between Rack A and Rack B. We break down the ACC cable and chip market here. There are multiple players with significant share. Furthermore, an additional 324 DensiLink flyover cables will be required for the OSFP cages. These DensiLink flyover cables alone are more than $10,000 of additional cost per NVL36x2.

NVL36x2 每套系統還需要額外 162 條 1.6T 雙埠水平 ACC cable,用來連接 Rack A 與 Rack B 之間的 NVSwitch tray,而這類線纜價格非常高。我們另有拆解 ACC cable 與相關晶片市場,其中有多家業者占有顯著份額。此外,還需要額外 324 條 DensiLink flyover cable 連到 OSFP cage;光是這些 DensiLink flyover cable,就會讓每套 NVL36x2 額外增加超過 10,000 美元成本。

Atomic Claim 37/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0037

Claim: NVL36x2 每套系統額外需要 162 條 1.6T twin-port horizontal ACC cables,用於連接 Rack A/B 的 NVSwitch trays。
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 38/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0038

Claim: NVL36x2 額外需要 324 條 DensiLink flyover cables,單此項增加成本超過 10,000 美元。
Frame: ATTRIBUTE · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

image

Source: SemiAnalysis

Moreover, it will require twice as many NVSwitch5 ASICs to enable the connection between Rack A and Rack B. This will bring the total NVLink copper cabling costs up by more than double versus NVL72.

此外,為了讓 Rack A 與 Rack B 之間能夠互連,NVL36x2 所需的 NVSwitch5 ASIC 數量會增加一倍,這使其 NVLink 銅纜總成本相較 NVL72 提高超過一倍。

Atomic Claim 39/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0039

Claim: NVL36x2 因跨 rack 連接需要約兩倍 NVSwitch5 ASIC,NVLink copper cabling 成本也超過 NVL72 的兩倍。
Frame: COMPARISON · Mode: ASSERTED · Mapping: PARTIAL
開啟逐條審核

Even though the NVLink backplane content is more than twice as expensive for NVL36x2 vs NVL72, most customers will opt for the NVL36x2 design due to power and cooling constraints which we will discuss below. To be clear while it is very pricey, both NVL36x2 and NVL72 have lower copper costs than the investor community thinks.

雖然 NVL36x2 的 NVLink backplane 價值量比 NVL72 高出兩倍以上,但由於後文會談到的電力與散熱限制,多數客戶仍會選擇 NVL36x2。需要強調的是,雖然這套互連確實很昂貴,但無論 NVL36x2 或 NVL72,其實際銅互連成本都低於投資人普遍想像。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

The real winner is the cabling vendors and active copper chip vendors in the supply chain who have a massive increase in volumes for leading edge 1.6T due to the prevalence of NVL36x2.

真正受惠的是供應鏈中的線纜廠與 active copper 晶片供應商。由於 NVL36x2 普及,最先進 1.6T 產品的出貨量將大幅增加。

GB200 NVL576

As Jensen mentioned on stage, GB200 NVLink can connect to 576 Blackwell GPUs together. We believe this is done using a 2 tier fat tree topology with 18 planes. This is similar to what they planned for DGX H100 NVL256 to connect 16 NVL36 racks. It will use 288 L1 NVSwitch5 ASICs (144 1U switch trays) located in the compute racks like NVL36x2, and it will use 144 L2 NVSwitch ASICs (72 2U switch trays) located on dedicated NV Switch trays. Like NVL36x2, the connection between the GPUs and the L1 NVSwitch will use the same copper backplane since it is over a short distance.

如 Jensen 在台上所說,GB200 NVLink 可以把 576 顆 Blackwell GPU 連在一起。我們認為其作法是採用 18 個 plane 的兩層 fat-tree 拓樸,與先前規劃中的 DGX H100 NVL256 類似,後者原本要連接 16 個 NVL36 機櫃。NVL576 會使用 288 顆 L1 NVSwitch5 ASIC(144 個 1U switch tray),放在與 NVL36x2 類似的 compute rack 中;另外再使用 144 顆 L2 NVSwitch ASIC(72 個 2U switch tray),配置於專用 NVSwitch 機櫃。與 NVL36x2 相同,GPU 與 L1 NVSwitch 之間距離較短,因此仍採用相同的銅 backplane。

Atomic Claim 40/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0040

Claim: GB200 NVLink 的 NVL576 方案可連接 576 顆 Blackwell GPUs。
Frame: ATTRIBUTE · Mode: ATTRIBUTED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 41/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0041

Claim: SemiAnalysis 判斷 NVL576 採 2-tier fat-tree topology、18 planes。
Frame: ATTRIBUTE · Mode: INFERRED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 42/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0042

Claim: SemiAnalysis 預估 NVL576 使用 288 顆 L1 NVSwitch5 ASIC(144 個 1U trays)與 144 顆 L2 NVSwitch ASIC(72 個 2U trays)。
Frame: ATTRIBUTE · Mode: EXPECTED · Mapping: PARTIAL
開啟逐條審核

image

Source: SemiAnalysis

Unfortunately, between the L1 NVSwitch and the L2 NVSwitch, the distance is greater than what copper can achieve; thus, optical connections must be used. Furthermore, the L2 NVSwitches use Flyover cables to go to the OSFP cages on the front of the chassis. The additional BOM cost for NVL576 is astronomical at over $5.6 million dollars (9.7k per GPU) that Nvidia would need to pay to their suppliers.

但 L1 NVSwitch 與 L2 NVSwitch 之間的距離已超過銅互連可有效支援的範圍,因此必須使用光學連線。此外,L2 NVSwitch 還要透過 flyover cable 連到機箱前方的 OSFP cage。NVL576 額外增加的 BOM 成本非常驚人,Nvidia 光是支付給供應商就超過 560 萬美元,相當於每顆 GPU 約 9,700 美元。

Atomic Claim 43/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0043

Claim: NVL576 的 L1 與 L2 NVSwitch 距離超出 copper 可達範圍,因此必須採 optical connections。
Frame: RELATION · Mode: ASSERTED · Mapping: COMPLETE
開啟逐條審核

Atomic Claim 44/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0044

Claim: SemiAnalysis 估計 NVL576 額外 BOM 成本超過 560 萬美元,約每 GPU 9.7k 美元。
Frame: ATTRIBUTE · Mode: ESTIMATED · Mapping: COMPLETE
開啟逐條審核

Applying a blanket 75% gross margin means customers would need to pay an additional 38.8k per GPU for NVL576 copper + optical connections. While Nvidia can cut back on margins, even at 0% for the scale out NVLink solution, it’s basically untenable. This is the exact same reason to why DGX H100 NVL256 never shipped due to the massive cost of transceivers . Optics is far too expensive for the accelerator interconnect as the accelerator interconnect needs to be extremely high bandwidth.

若直接套用 75% 毛利率,客戶為 NVL576 的銅纜加光學互連,每顆 GPU 還要額外支付約 38,800 美元。即使 Nvidia 願意降低毛利,甚至 scale-out NVLink 解決方案完全不賺毛利,成本仍幾乎難以接受。這與 DGX H100 NVL256 最終未出貨的原因完全相同:transceiver 成本太高。由於 accelerator interconnect 需要極高頻寬,光學方案在這個用途上的成本仍遠高得難以承受。

Atomic Claim 45/45 · 2024-07-17_gb200-hardware-architecture-and-component::GB2-0045

Claim: 若假設 75% gross margin,SemiAnalysis 估計 NVL576 copper + optical connections 將增加約每 GPU 38.8k 美元的客戶成本。
Frame: ATTRIBUTE · Mode: ESTIMATED · Mapping: COMPLETE
開啟逐條審核

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

Backend Networking

The backend networking of GB200 is where most of the options crop up. Nvidia generally releases GPUs with the new generation of NIC and Switch ready to go, but this generation, due to Nvidia’s aggressive timelines, especially with 224G SerDes, the new networking comes halfway through the Blackwell generation. As such, all initial shipments of GB200 will utilize the same ConnectX-7 that shipped in the majority of H100 servers.

GB200 的 backend networking 是選項最多的部分。Nvidia 一般會在推出新一代 GPU 時,同步準備好新一代 NIC 與 switch;但這一代因開發時程非常積極,特別是導入 224G SerDes,新一代網路產品要到 Blackwell 世代中期才會到位。因此最初出貨的 GB200,全部都會沿用多數 H100 伺服器使用的 ConnectX-7。

For the Backend Networking there a handful of different types of switches that customers will use depending on which NIC they utilize.

在 backend networking 方面,客戶會依所採用的 NIC 不同,搭配數種不同類型的 switch。

Quantum-2 QM9700 Infiniband NDR

Quantum-2 QM9700 InfiniBand NDR

Quantum-X800 QM3400 Infiniband XDR

Quantum-X800 QM3400 InfiniBand XDR

Quantum-X800 QM3200 Infiniband NDR/XDR

Quantum-X800 QM3200 InfiniBand NDR/XDR

Spectrum-X SN5600

Spectrum-X Ultra

Broadcom Tomahawk 5

Broadcom Tomahawk 6

In terms of the backend networking, the time to market shipments will all be the QM9700 Quantum-2 switch or Broadcom Tomahawk 5 just like H100 geneartion. Despite it being the same backend networking hardware, there is a big challenge with utilizing rail optimized designs . This due to the port mismatch between the switch and how many ports there are on a rack. With NVL72, there are 4 GPUs per compute tray, which means in a 4 rail optimized design, each Quantum-2 switch should have 18 downlink ports.

就 backend networking 而言,為了搶先上市,初期出貨都會採用與 H100 世代相同的 QM9700 Quantum-2 switch 或 Broadcom Tomahawk 5。雖然 backend networking 硬體相同,但要採用 rail-optimized 設計會遇到很大的挑戰,原因是 switch port 數量與單櫃所需 port 數不匹配。NVL72 每個 compute tray 有 4 顆 GPU,因此在 4-rail optimized 設計下,每台 Quantum-2 switch 應該配置 18 個 downlink port。

image

Source: SemiAnalysis

Since each switch has the same number of uplink ports in a fat tree, that means only 36 out of the 64 ports will be used. In effect, each switch will have many idle ports. If 2 rails went to each switch, then that would be 72 ports which will be over what the QM9700 Quantum-2 switch offers. In order to utilize all ports within each Quantum-2 switch, there will be 9 non-rail optimized leaf switches for every 4 NVL72 rack.

由於 fat-tree 中每台 switch 的 uplink port 數量與 downlink 相同,因此 64 個 port 中只會用到 36 個,等於每台 switch 都會有大量閒置 port。如果每台 switch 承接 2 個 rail,則需要 72 個 port,又超過 QM9700 Quantum-2 能提供的數量。為了把每台 Quantum-2 的 port 都充分利用,每 4 個 NVL72 機櫃需要配置 9 台非 rail-optimized 的 leaf switch。

image

Source: Nvidia

For ConnectX-7, you can also use the Q3200 Quantum-3 switch tray which contains 2 independent switches, each with 36 400Gb/s ports. This does not have a port mismatch and can use 4-rail optimized with 4 Q3200 Quantum-X800 Switch per NVL72.

ConnectX-7 也可以搭配 Q3200 Quantum-3 switch tray;每個 tray 內含 2 台彼此獨立的 switch,每台有 36 個 400Gb/s port。這個方案沒有 port mismatch,因此 NVL72 可以採用 4-rail optimized 設計,每個 NVL72 配置 4 台 Q3200 Quantum-X800 switch。

image

Source: Nvidia

For the upgraded 800Gb/s ConnectX-8, which will ship starting Q2 2025 with Quantum-X800 Q3400 which has 144 800Gb/s ports distributed across 72 twin port OSFP ports. Since there is no port mismatch, most customers will choose the Nvidia recommended design of 4-rail optimized with the switch rack being end of rack (EoR).

升級至 800Gb/s 的 ConnectX-8 預計自 2025 年第二季開始出貨,搭配 Quantum-X800 Q3400;Q3400 具備 144 個 800Gb/s port,分布在 72 個雙埠 OSFP port 上。由於不存在 port mismatch,多數客戶會採用 Nvidia 建議的 4-rail optimized 設計,並將 switch rack 置於 end-of-rack(EoR)。

With CX-8, you can also use Spectrum-X Ultra 800G, forgoing the costly and expensive Bluefield option that was required in the prior generation. We discuss the Quantum-X800 switch option here and how it will affect the optical transceiver market. Broadcom based Tomahawk 6 deployment variants will also arrive in the 2nd half of next year.

搭配 CX-8 時,也可以使用 Spectrum-X Ultra 800G,並省去前一代所需、成本很高的 BlueField 選項。我們另有討論 Quantum-X800 switch 方案,以及它將如何影響 optical transceiver 市場。採用 Broadcom Tomahawk 6 的部署版本,也會在明年下半年陸續推出。

image

Source: SemiAnalysis

The transition from CX-7 to CX-8 will be the main impetus for the shift from 400G (4x100G) SR4 optical transceivers to 800G (4x200G) DR4 optical transceivers. With CX-7 on the GB200 NVL72, each GPU has 400G of bandwidth and is connected to one OSFP cage with the multimode 400G Single-Port SR4 transceiver with four optical lanes each powered by a multimode 100G VCSEL. With a CX-7 based network, the switch side usually employs the 800G twin-port SR8 or DR8 transceiver.

從 CX-7 升級到 CX-8,將是光模組從 400G(4×100G)SR4 轉向 800G(4×200G)DR4 的主要推動力。在採用 CX-7 的 GB200 NVL72 中,每顆 GPU 有 400G 頻寬,連到 1 個 OSFP cage,並使用單埠 multimode 400G SR4 transceiver;其中有 4 條 optical lane,每條由一顆 multimode 100G VCSEL 驅動。CX-7 網路的 switch 端通常使用 800G 雙埠 SR8 或 DR8 transceiver。

For CX-8, all the speeds double, 800G (4x200G) DR4 per GPU and 1.6T(8x200G) DR8 per OSFP cage on the switch end. Because development work on the 200G multimode VCSEL will not complete for another 9 to 18 months for the 1.6T ramp, the industry has instead turned to the single mode 200G EML instead.

到了 CX-8,所有速度都會加倍:每顆 GPU 為 800G(4×200G)DR4,而 switch 端每個 OSFP cage 則為 1.6T(8×200G)DR8。由於 200G multimode VCSEL 的開發還需要約 9–18 個月,趕不上 1.6T ramp,產業因此轉而採用 single-mode 200G EML。

Similar to DGX H100, Cedar-8 will be available where both CX-8 NIC ICs from each Bianca board goes into a single OSFP224 cage **. **The advantages of requiring two 1.6T (8x200G lanes) twin port transceivers instead of four 800G(4x200G lanes) single port transceivers. Since a single port 4x200G transceiver is approximately 35% less expensive than an 8x200G twin port transceiver, by using Cedar-8 instead of two 4x200G transceivers, the cost will be 30% lower. Due to the cooling challenges of having 2x as much bandwidth in a single OSFP cage on the compute tray, we expect that most firms will not be using the Cedar-8.

與 DGX H100 類似,也會提供 Cedar-8;每張 Bianca board 上的兩顆 CX-8 NIC IC 會共同連到單一 OSFP224 cage。這樣只需要 2 個 1.6T(8×200G lane)雙埠 transceiver,而不是 4 個 800G(4×200G lane)單埠 transceiver。由於單埠 4×200G transceiver 的價格約比 8×200G 雙埠 transceiver 低 35%,使用 Cedar-8 取代兩組 4×200G transceiver,成本可降低約 30%。不過 compute tray 上單一 OSFP cage 的頻寬增加一倍,也帶來更大的散熱挑戰,因此我們預期多數業者不會採用 Cedar-8。

Most firms will be sticking to ConnectX-7/ConnectX-8 at launch. Even firms such as Google, that have historically used custom backend NICs from the likes of Intel, will be switching back to the Nvidia ConnectX-8 NICs.

大多數業者在初期仍會採用 ConnectX-7/ConnectX-8。甚至像 Google 這類過去曾使用 Intel 等供應商客製 backend NIC 的公司,也會重新改用 Nvidia ConnectX-8 NIC。

The only exception that will integrate their own backend NIC will be Amazon. We believe they will use their custom backend 400G (4x100G) NIC. This networking card will be different from their standard Nitro NICs as it will mostly be performance oriented.

唯一會整合自家 backend NIC 的例外是 Amazon。我們認為 Amazon 會採用自研的 400G(4×100G)backend NIC;這張網卡會與其標準 Nitro NIC 不同,設計重點將更偏向效能。

image

Source: SemiAnalysis

In order to use custom backend NICs on the Bianca board instead of using ConnectX ICs on the mezzanine board, they will need to use an adapter mezzanine board that splits from the mirror mezz connectors into 8 MCIO PCIe connectors that go to the front of the chassis.

若要在 Bianca board 上使用客製 backend NIC,而不是使用 mezzanine board 上的 ConnectX IC,就需要一張 adapter mezzanine board,將 Mirror Mezz connector 的訊號分拆成 8 個 MCIO PCIe connector,並延伸到機箱前方。

image

Source: HighYieldYT

Since there will be no ConnectX-7/8 or Bluefield-3, which both have integrated PCIe switches, a dedicated PCIe switch from Broadcom / Astera Labs will be required to connect the backend NICs to both the CPU and GPU. In SemiAnalysis GB200 Component & Supply Chain Model , we breakdown the PCIe switch supplier, volume, and ASP. There are still hyperscaler custom design that includes PCIe Switches for between the CPU and NICs. Nvidia’s Miranda design is also quite different than GB200 on PCIe Lane Handling. Furthermore Amazon Trainium 2 deployments have large amounts of Astera Labs retimer content .

由於系統不再配置 ConnectX-7/8 或 BlueField-3,而這些晶片本身都整合了 PCIe switch,因此必須額外使用 Broadcom/Astera Labs 的獨立 PCIe switch,把 backend NIC 同時連到 CPU 與 GPU。我們在 SemiAnalysis GB200 Component & Supply Chain Model 中拆解了 PCIe switch 的供應商、出貨量與 ASP。仍有一些 hyperscaler 客製設計會在 CPU 與 NIC 之間加入 PCIe switch。Nvidia 的 Miranda 設計在 PCIe lane handling 上也與 GB200 有顯著差異;此外,Amazon Trainium 2 部署中也含有大量 Astera Labs retimer。

Using a custom NIC brings extra engineering work to firms as they can’t use the default water cooling block which is engineered to cool the ConnectX ICs too. They would also need to run fresh thermal simulations to ensure that custom NICs in the front of the chassis have enough cooling capacity to not cause overheating problems. Moreover, they will not be able to use the 1U compute tray version used in NVL72.

使用客製 NIC 也會增加額外工程工作,因為業者無法直接沿用預設的水冷 block;原本的水冷 block 同時也負責替 ConnectX IC 散熱。若改用客製 NIC,還必須重新進行熱模擬,確認機箱前方的客製 NIC 有足夠散熱能力、不會造成過熱。此外,這種方案也無法採用 NVL72 所使用的 1U compute tray。

They can only opt for the 2U NVL36 version which has enough air-cooling capacity at the front of the tray. All of this extra engineering work will delay the time to market for Amazon and anybody else attempting to use custom backend NICs. These challenges are why Google opted to use ConnectX-8 instead of continuing to use Intel’s IPUs for their GB200 servers.

這類客戶只能選擇 2U NVL36 版本,因為 tray 前方有足夠的氣冷能力。所有額外工程工作都會拖慢 Amazon,以及其他嘗試使用客製 backend NIC 業者的上市時程。這些挑戰也是 Google 在 GB200 伺服器上選擇 ConnectX-8,而不再延續 Intel IPU 的原因。

Frontend Networking

In the reference design, there are two 400Gb/s Bluefield-3 per compute tray. Since there are 4 GPUs per compute tray, that would mean that each GPU gets 200Gb/s of frontend bandwidth. The most advanced HGX H100 server deployed today has a single 200-400Gb/s ConnectX-7 NIC for their frontend traffic. That is for 8 GPUs, meaning 25-50Gb/s per GPU. 200Gb/s of frontend bandwidth per GPU is an extreme amount and most customers will not opt for this additional cost. In general, the Nvidia reference design is overprovisioned for the absolute worst-case situation for them to sell you more content.

reference design 每個 compute tray 配置 2 顆 400Gb/s BlueField-3。由於每個 compute tray 有 4 顆 GPU,等於每顆 GPU 可分到 200Gb/s frontend bandwidth。現今最先進的 HGX H100 部署,frontend traffic 通常只配置 1 張 200–400Gb/s ConnectX-7 NIC,供 8 顆 GPU 共用,也就是每顆 GPU 約 25–50Gb/s。每顆 GPU 配到 200Gb/s frontend bandwidth 顯然非常充裕,多數客戶不會願意為這麼高的配置支付額外成本。整體而言,Nvidia reference design 是按照最極端 worst-case 情境過度配置,這也能讓 Nvidia 賣出更多零組件。

image

Source: SemiAnalysis

We believe that the only major customer that will use Bluefield-3 as a frontend NIC will be Oracle. They run a cloud service that needs frontend network virtualization but have deployed a custom NIC solution, unlike the other hyperscalers. Amazon, Google, & Microsoft all have custom frontend NICs that are present in all their general-purpose CPU servers and accelerated computing servers already. They intend to continue to use these solutions as they offer a great TCO advantage and are already vertically integrated into their networking/cloud software stack.

我們認為唯一會把 BlueField-3 當作 frontend NIC 使用的主要客戶是 Oracle。Oracle 提供雲端服務,需要 frontend network virtualization,但不像其他 hyperscaler 一樣已經部署自研 NIC。Amazon、Google 與 Microsoft 在一般用途 CPU 伺服器與 accelerated computing server 中,都早已使用自己的客製 frontend NIC,未來也會繼續採用,因為這些方案具有明顯的 TCO 優勢,而且早已垂直整合進各自的網路與雲端軟體 stack。

Ironically, the only firm (xAI) that has widely used Bluefield-3 for the AI cluster is not even using it for its intended DPU purpose. xAI is using their Bluefield-3 in NIC mode instead of DPU mode since first-generation Nvidia Spectrum-X Ethernet requires Bluefield-3 for backend NICs as a bandage solution. Spectrum-X800 Ultra will work with CX-8 backend NICs and will not require Bluefield-3/4s to operate properly.

諷刺的是,目前唯一在 AI cluster 大量使用 BlueField-3 的公司 xAI,甚至不是把它拿來做原本設計的 DPU 功能。xAI 是以 NIC mode、而不是 DPU mode 使用 BlueField-3,因為第一代 Nvidia Spectrum-X Ethernet 需要 BlueField-3 作為 backend NIC,算是一種權宜解法。Spectrum-X800 Ultra 則可以直接搭配 CX-8 backend NIC,不再需要 BlueField-3/4 才能正常運作。

image

Source: SemiAnalysis, Michael Dell

Networking Cables + Transceivers Bill of Materials

Below, we have calculated the Bill of Material costs Nvidia pays their contract manufacturers. We will be only calculating the cost of the transceivers on the compute/NVSwitch tray end as the calculations get complex if you include switches, as clusters can be tier 2 or tier 3, or even 4 tiers in giant clusters.

下方我們計算了 Nvidia 支付給合約製造商的 BOM 成本。這裡只計算 compute tray/NVSwitch tray 端的 transceiver 成本;如果把 switch 也納入,計算會複雜許多,因為 cluster 可能是 2-tier、3-tier,超大型 cluster 甚至可能達到 4-tier。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

You can see that with ConnectX-8, by using a Top of Rack design with DAC/ACC copper instead of a 4-rail optimized backend design; there are savings of ~$32k for just the backend network alone. Unfortunately, due to the tight power requirements of the compute racks, we believe that most people will have to put their backend switches in a different service rack and use optics to connect between them.

可以看到,在 ConnectX-8 架構下,如果 backend 採 Top-of-Rack 設計並使用 DAC/ACC 銅纜,而不是 4-rail optimized backend design,光 backend network 就能節省約 32,000 美元。不過 compute rack 的電力餘裕非常有限,我們認為多數業者仍必須把 backend switch 放到另一個 service rack,再透過光學連線互連。

For the out of band management, this is all cheap copper RJ45 cables that cost less than a dollar each to connect from the compute/switch trays to the top of the rack out of band management switch. As mentioned above, the reference design is overkill for how much frontend NICs and bandwidth they have. We believe that most firms will have 200G of frontend bandwidth instead of having 2 BF-3 which is 800Gb/s of bandwidth in total per compute tray. This will lead to a saving of $3.5k per system just in transceiver costs alone.

out-of-band management 使用的都是便宜 RJ45 銅纜,每條不到 1 美元,用來把 compute/switch tray 連到 rack 頂端的 out-of-band management switch。如前所述,reference design 在 frontend NIC 數量與頻寬上都配置過度。我們認為多數業者每個 compute tray 只會配置 200G frontend bandwidth,而不是使用 2 顆 BF-3、合計提供 800Gb/s。光 transceiver 成本,每套系統就可因此節省約 3,500 美元。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

On the optics and DSPs, Nvidia is expanding the supply chain greatly to Eoptolink from just Fabrinet and Innolight who were the vast majority. Eoptolink is focusing on 800G LPO and 1.6T with DSP.

在 optics 與 DSP 方面,Nvidia 大幅擴大供應鏈,除了原本占絕大多數份額的 Fabrinet 與 Innolight,也納入 Eoptolink。Eoptolink 主要聚焦 800G LPO 與搭載 DSP 的 1.6T 產品。

The DSP game also changes massively. While Marvell was 100% share on Nvidia last generation with H100. This generation, Broadcom comes in a big way. We see both Innolight and Eoptolink looking to be adding Broadcom in volume for the DSP.

DSP 的競爭格局也大幅改變。上一代 H100 時,Marvell 在 Nvidia 的 DSP 供應上占 100% 份額;這一代 Broadcom 大舉切入,我們看到 Innolight 與 Eoptolink 都準備大批量導入 Broadcom DSP。

Furthermore, Nvidia has hired a number of DSP engineers and taped out a 1.6T DSP. We do not believe this will ramp in the near term, but if it does, it will be on the Fabrinet transceivers. The biggest challenge to ramping up the internal DSP is that Nvidia has used primarily the same long reach high power SerDes on each side of the DSP. Typically, DSPs have differently optimized SerDes on the optics facing vs NIC/Switch facing sides. Both sets of SerDes are optimized for power more than reach alone which was Nvidia’s main optimization point when they designed their 224G SerDes. Nvidia’s internal DSP guzzle too much power, and as such their in-house DSP is too difficult to ramp production of due to cooling challenges in the already toasty 1.6T transceivers. Nvidia’s DSP can also function as a retimer if needed, but the ACCs are enough.

此外,Nvidia 已招募多名 DSP 工程師,並完成一顆 1.6T DSP 的 tape-out。我們不認為這顆晶片短期內能大量 ramp;若真的導入,較可能先用在 Fabrinet 的 transceiver。Nvidia 自研 DSP 最大的量產挑戰,在於 DSP 兩側主要使用同一類 long-reach、高功耗 SerDes。一般 DSP 在面向 optics 與面向 NIC/switch 的兩側,會使用不同方向最佳化的 SerDes;兩側通常都更著重功耗,而不只是追求傳輸距離。Nvidia 在設計 224G SerDes 時主要最佳化的是 reach,導致自研 DSP 功耗過高。在原本就已經很熱的 1.6T transceiver 中,散熱問題使其自研 DSP 很難大量生產。Nvidia 的 DSP 必要時也能當 retimer 使用,但 ACC 已足以滿足需求。

We have market share and ASP of Optics provider and DSPs in the SemiAnalysis GB200 Component & Supply Chain Model .

SemiAnalysis GB200 Component & Supply Chain Model 中整理了 optics 供應商與 DSP 的市占率及 ASP。

Get 20% off a group subscription

團體訂閱可享 8 折優惠

The above only covered the high level and basics, but below, we will dive into all the subcomponents and BOM on the GB200 including substrate, PCB, CCL, Substrate, liquid cooling, Sidecars, CDUs, UQDs, Manifolds, Vapor Chambers, Cold Plates, BMCs, and Power Delivery below. We will also cover more on the hyperscale customization. We will also cover all the complexities and decision matrices for liquid cooling supply chain selections.

以上只涵蓋高層次架構與基本概念。接下來我們會深入 GB200 的所有子零組件與 BOM,包括 substrate、PCB、CCL、液冷、sidecar、CDU、UQD、manifold、vapor chamber、cold plate、BMC 與 power delivery,也會進一步分析 hyperscaler 客製化,以及液冷供應鏈選擇中的各種複雜因素與決策矩陣。

Substrate, PCB, and CCL

Due to the system architecture changes and higher IO / power density, the organic package substrate, CCL (copper clad laminate), glass fiber, and PCB all have big complexity increases from Blackwell HGX and GB200.

由於系統架構改變,加上 I/O 與功率密度提高,Blackwell HGX 與 GB200 所使用的有機封裝基板、CCL(copper clad laminate)、玻纖與 PCB,複雜度都大幅提升。

The substrate which the Blackwell GPU sits on is larger and also has 2 more layers. In the prior generation, Ibiden dominated with 100% share. This generation, Unimicron becomes a second source of ABF substrates to Ibiden for Blackwell GPU. Moreover, Unimicron is the main supplier of ABF for Grace CPU with Ibiden as second. Unimicron is moving up their capacity expansion dedicated to Nvidia dramatically from 1Q25 to 3Q24 due to big increases in GB200 demand vs B100/B200. Ibiden will still grow, but Unimicron is taking a lot of the slack up.

Blackwell GPU 所使用的 substrate 尺寸更大,而且層數也比前一代多 2 層。上一代由 Ibiden 獨占、占 100% 份額;這一代 Unimicron 成為 Blackwell GPU ABF substrate 的第二供應商。另一方面,Grace CPU 的 ABF 主要供應商則是 Unimicron,Ibiden 為第二供應商。由於 GB200 需求相較 B100/B200 大幅增加,Unimicron 把原本規劃在 2025 年第一季、專門供 Nvidia 的擴產時程大幅提前到 2024 年第三季。Ibiden 仍會成長,但相當一部分新增需求將由 Unimicron 承接。

We should note there have been significant problems with CoWoS-L ramps for Nvidia , and all the other issues people keep murmuring about are minor in comparison.

需要注意的是,Nvidia 的 CoWoS-L ramp 確實遇到相當嚴重的問題;相較之下,市場上其他流傳的問題都只是次要因素。

For the HGX architecture, there are two main boards, the SXM board, the UBB (universal baseboard). One GPU is attached to each SXM board, then 8 SXMs are placed onto one UBB.

HGX 架構主要有兩類板件:SXM board 與 UBB(universal baseboard)。每張 SXM board 安裝 1 顆 GPU,接著 8 張 SXM 再裝到 1 張 UBB 上。

image

Source: SemiAnalysis

For GB200 architecture, this completely changes as described above. The primary Bianca board is significantly more complex per GPU due to the addition of the CPU, collapse to higher density board with higher power / more IO density. Furthermore, there are a variety of complex daughterboards that demand high grade CCL (M7+) such as the mezzanine ConnectX-7/8. This is because it runs in switch mode connecting the CPU and GPU to each NIC. The NVSwitch board also requires high grade M7 CCL.

到了 GB200,架構如前所述完全改變。主要的 Bianca board 因加入 CPU、把系統壓縮到更高密度,且功率與 I/O 密度都提高,因此以每顆 GPU 來看,板件複雜度顯著增加。此外,系統中還有多種複雜 daughterboard,需要使用高階 CCL(M7+),例如 ConnectX-7/8 mezzanine board,因為它會以 switch mode 運作,把 CPU 與 GPU 都連到每顆 NIC。NVSwitch board 同樣需要高階 M7 CCL。

image

Source: SemiAnalysis

The copper clad laminate for Hopper SXM was sole source from EMC and they were the majority supplier on the UBB board as well. With Blackwell, they are losing share on Blackwell SXM and Bianca boards to Doosan. This is likely due to price competition from Doosan, in which EMC chooses not to engage with as EMC will achieve full utilization rates in 3Q24 with other high margin projects like ASICs and LEO Satellites. Lastly, NVSwitch board CCL is M7 grade HDI and is sole supplied by EMC.

Hopper SXM 所使用的 copper clad laminate 由 EMC 單一供應,EMC 在 UBB board 上也占主要份額。到了 Blackwell,EMC 在 Blackwell SXM 與 Bianca board 上的份額被 Doosan 搶走一部分。我們認為主要原因是 Doosan 的價格競爭,而 EMC 選擇不跟進,因為 2024 年第三季 EMC 透過 ASIC、LEO satellite 等高毛利專案就能達到滿載。至於 NVSwitch board,其 CCL 為 M7 等級 HDI,仍由 EMC 單一供應。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

Despite the big win, Doosan does not have enough capacity. We estimate nearly 1.9 million sheets a month are required to meet Nvidia’s demand based on our house view split between GB200 and HGX shipment for Blackwell. EMC has more than double of Doosan’s capacity at 4.3mn sheets/month in 3Q24. EMC planned to expand capacity in 2025 by 1.2mn sheets/month to meet the extra demand that Nvidia has and Doosan cannot fulfill. There will be a consistent trend of requiring higher grade CCL (M7+) and higher layer count PCBs that will drive PCB materials businesses stronger.

儘管 Doosan 拿下大單,但其產能並不足以完全滿足需求。根據我們對 Blackwell 在 GB200 與 HGX 出貨占比的 house view,估計每月需要接近 190 萬張 CCL 才能滿足 Nvidia 需求。EMC 在 2024 年第三季的產能約為每月 430 萬張,是 Doosan 的兩倍以上。EMC 原本規劃 2025 年再增加每月 120 萬張產能,以承接 Nvidia 額外需求中 Doosan 無法供應的部分。未來持續朝更高階 CCL(M7+)與更多 PCB 層數發展,將持續帶動 PCB 材料業務成長。

Doosan’s CCL business unit contributed only 4.1% of its revenue in 1Q24, but this will soar. Interestingly, Doosan is not only exposed to the AI theme through its CCL business. Doosan also has a subsidiary – Doosan Enerbility which has meme stock potential given its partnership with NuScale and supplies them with the small modular nuclear reactors which some want to power datacenters with .

Doosan 的 CCL 事業部在 2024 年第一季只占公司營收 4.1%,但未來這個比重將大幅上升。有趣的是,Doosan 對 AI 題材的曝險不只來自 CCL;公司還有子公司 Doosan Enerbility,因與 NuScale 合作、並供應 small modular nuclear reactor(SMR),也具備所謂 meme stock 的想像空間,而部分市場人士希望未來能用這類核能設施為資料中心供電。

Glass fiber cloth is a key raw material of CCL. Currently, the glass fiber cloth market (NE grade) required for AI server application is dominated by Japanese suppliers, notably Nitto Boseki and Asahi Kasei. Nitto Boseki has about 60% market share of NE grade glass fiber cloth and is currently supplied constraint. The difference between Nitto Boseki and Asahi Kasei is the glass fiber yarn manufacturing capacity which is the upstream material to make glass fiber cloth. Nitto Boseki has glass fiber yarn capacity which they can use internally and sell externally. Naturally, Nitto Boseki will prioritize the glass fiber yarn supply for themselves. Asahi Kasei, on the other hand, probably needs to source from AGY who supplies the glass fiber yarn.

玻纖布是 CCL 的關鍵原材料。目前 AI server 所需的 NE grade 玻纖布市場主要由日本供應商主導,尤其是 Nitto Boseki 與 Asahi Kasei。Nitto Boseki 約占 NE grade 玻纖布 60% 市占,目前供給受限。Nitto Boseki 與 Asahi Kasei 的主要差異在於 glass fiber yarn 產能;這是製造玻纖布的上游材料。Nitto Boseki 自有 glass fiber yarn 產能,既能內部使用也能外售,自然會優先保障自家供應。Asahi Kasei 則可能需要向 AGY 採購 glass fiber yarn。

Keeping It Cool: Liquid Cooling Analysis

As thermal design power (TDP) increases from 700W for H100 to 1000W/1,200W for B200/GB200, the second biggest shift from Hopper to Blackwell hardware besides connectivity/networking is the adoption of direct-to-chip liquid cooling (DLC) to increase compute density on the rack level. This translates to an 7-20 times increase in cooling content per GPU compared to DGX H100 depending on the GB200 SKU as well as the split between liquid to air (L2A) and liquid to liquid (L2L) solutions.

隨著 thermal design power(TDP)從 H100 的 700W,提高到 B200/GB200 的 1000W/1200W,除了 connectivity/networking 之外,Hopper 升級 Blackwell 的第二大硬體變化,就是採用 direct-to-chip liquid cooling(DLC),以提高 rack level 的運算密度。依 GB200 SKU 不同,以及 liquid-to-air(L2A)與 liquid-to-liquid(L2L)方案占比不同,每顆 GPU 的散熱價值量相較 DGX H100 將增加約 7–20 倍。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

Air cooling is widely adopted for H100 HGX servers using 3DVC (3D vapor chamber) and fans. However, this comes with a sacrifice, at up to 10.2kW TDP per server, sufficient rack space is required to accommodate 4 rack unit tall (1 rack unit = 1.75in) 3DVC to dissipate heat effectively. 8xH100 HGXX servers are generally around 5-8RU tall. Each rack usually has 2-4 H100 HGX nodes, so the TDP for each rack is around 20-40kW.

H100 HGX server 普遍採用 3DVC(3D vapor chamber)與風扇進行氣冷。不過這會犧牲機櫃空間:當單台伺服器 TDP 高達 10.2kW 時,需要足夠的 rack space,容納高度約 4RU(1RU = 1.75 吋)的 3DVC,才能有效散熱。8×H100 HGX server 通常高約 5–8RU,而每個 rack 一般配置 2–4 個 H100 HGX node,因此單櫃 TDP 約為 20–40kW。

For Blackwell, the B100’s and B200’s TDP are at 700W and 1000W/1200W respectively, which requires even taller 3DVC or cold plates for direct liquid cooling (DLC). With the 2700W GB200 Bianca board, DLC is the only option. The chassis height per compute tray to drop to 1-2 RU for GB200, compared to the 9-10RU chassis height of an air-cooled B200 HGX server.

Blackwell 中,B100 與 B200 的 TDP 分別約為 700W 與 1000W/1200W,因此需要更高的 3DVC,或改用 direct liquid cooling(DLC)的 cold plate。對 2700W 的 GB200 Bianca board 而言,DLC 是唯一可行方案。GB200 每個 compute tray 的 chassis height 可降到 1–2RU,而採氣冷的 B200 HGX server 則需要約 9–10RU 高度。

Besides the increase compute density, another motivation to adopt DLC is the gain on energy efficiency as total data center power lowers by more than 10.2% for DLC L2L solution. In this section we will talk about the implication of this architectural shift of cooling solution on DLC hardware supply chain, data center architecture, different DLC form factors, and CSP/end customers procurement dynamic.

除了提高運算密度之外,採用 DLC 的另一個動機是能源效率提升;使用 DLC L2L 方案後,整體資料中心耗電可降低超過 10.2%。本節會討論這項散熱架構轉變對 DLC 硬體供應鏈、資料中心架構、不同 DLC form factor,以及 CSP/終端客戶採購模式的影響。

Redesigning Rack Architecture for DLC

DLC requires more components than air cooling to deploy. While air cooling solution hardware consists of Thermal Interface Material (TIM), Integrated Heat Spreader (IHS) (100% supplied by Jentech), 3DVC, and fans. liquid cooling solutions replace the 3DVC and the fans with these following components:

DLC 部署所需的零組件比氣冷更多。氣冷方案的硬體主要包含 Thermal Interface Material(TIM)、Integrated Heat Spreader(IHS,100% 由 Jentech 供應)、3DVC 與風扇;液冷方案則會用以下零組件取代 3DVC 與風扇:

Cold Plate - dissipates and spreads heat within a copper plate and transfers heat through a liquid loop.

Cold Plate-在銅板內吸收並擴散熱量,再透過液體迴路把熱帶走。

Quick Disconnects (QD) - allow the connection and disconnection of fluid lines in a fast and convenient way, without loss of fluids.

Quick Disconnect(QD)-可快速、方便地連接與拆卸液體管線,同時避免冷卻液流失。

Coolant Distribution Manifolds (CDM) - supplies cold coolant to each server and returns warm coolant back to the CDU.

Coolant Distribution Manifold(CDM)-把低溫冷卻液供應到每台伺服器,再把升溫後的冷卻液送回 CDU。

Liquid to Air Coolant Distribution Units (L2A CDU), also known as sidecar, which includes:

Liquid-to-Air Coolant Distribution Unit(L2A CDU),也稱為 sidecar,包含:

Reservoir and Pump Unit (RPU), which includes:

Reservoir and Pump Unit(RPU),包含:

Pump – pushes and circulates the coolant throughout the liquid cooling system (2N design for redundancy).

Pump-推動並循環液冷系統中的冷卻液,採 2N 設計以提供冗餘。

Water Tank (Reservoir) - facilitates easy filling and expansion to avoid pressure build up and helps in removing air bubbles.

Water Tank(Reservoir)-方便系統補充冷卻液與容納液體膨脹,避免壓力累積,同時有助於排除氣泡。

Radiators - releases the heat absorbed into the air

Radiator-把吸收的熱量釋放到空氣中。

Fans – blow the air away form the radiator

Fan-把通過 radiator 的熱空氣吹走。

Liquid to Liquid Coolant Distribution Units (L2L CDU), which includes:

Liquid-to-Liquid Coolant Distribution Unit(L2L CDU),包含:

RPU

Brazed Plate Heat Exchanger (BPHE) - creates flowing channels between plates, with one fluid in odd number channels and the other in the even number channels, thus reaching the purpose of heat exchanging.

Brazed Plate Heat Exchanger(BPHE)-在板片之間形成流道,讓一種液體流過奇數通道、另一種液體流過偶數通道,藉此進行熱交換。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

We estimated the liquid cooling components dollar content by the NVL72 and the NVL72 (36*2) system and by different CDU form factor. The graph shows that adopting L2L CDU is much more economical than adopting L2A form factor, given the much higher price per W ratio for L2A CDU.

我們依 NVL72、NVL72(36×2)系統,以及不同 CDU form factor,估算液冷零組件的金額含量。圖中顯示,採用 L2L CDU 的經濟性明顯優於 L2A,因為 L2A CDU 的每瓦成本高出許多。

Heat Transfer Flow from the Chip

For air cooling: Heat from the chip is conducted through the TIM (thermal interface material) to be evenly distributed among the area of the heat spreader.

在氣冷方案中,晶片產生的熱會先透過 TIM(thermal interface material)傳導,再均勻分布到 heat spreader 的表面。

image

Source: TSMC

Then, the heat goes to the 3DVC, where the heat enters the vapor chamber and travels up the heat pipe into the heat sink. Then, air flow from the fan carries the heat away from the heat sink away from the chassis.

接著熱會傳到 3DVC,進入 vapor chamber,再沿 heat pipe 傳到 heat sink。最後,風扇產生的氣流把 heat sink 上的熱帶走並排出機箱。

image

Source: Nextron

For DLC solution: the heat transfer from IHS to the cold plate and the coolant inside the coldplate absorbs the heat and carries it away to the cooling distribution manifold (CDM). Then, the CDM collects all the coolant from each tray and it goes to the CDU where the coolant exchanges heat with the surrounding air/water through the radiator/BPHE depending on whether it is L2L or L2A. The cooled coolant returns to the CDM, where the coolant is distributed back to each tray. Finally, the coolant enters the cold plate again repeating the process.

在 DLC 方案中,熱先從 IHS 傳到 cold plate,cold plate 內的冷卻液吸收熱量後,把熱帶到 cooling distribution manifold(CDM)。CDM 收集每個 tray 回流的冷卻液,再送到 CDU;依採用 L2L 或 L2A 不同,冷卻液會透過 radiator/BPHE 與周圍空氣或水進行熱交換。降溫後的冷卻液再回到 CDM,重新分配到各個 tray,最後再次進入 cold plate,重複整個循環。

image

Source: Boyd

Despite the Bianca board, including two B200 GPUs, one Grace CPU, and two Connect-X NICs, will be liquid cooled, the front half of the GB200 compute tray and NVSwitch tray, where the custom NICs/DPU, PDU, and the management board sit, are air-cooled. Hence, the compute tray will be ~85% liquid cooled and ~15% air-cooled.

雖然 Bianca board 上的 2 顆 B200 GPU、1 顆 Grace CPU 與 2 顆 ConnectX NIC 都採液冷,但 GB200 compute tray 與 NVSwitch tray 的前半部仍採氣冷,因為客製 NIC/DPU、PDU 與 management board 都位於這個區域。因此整個 compute tray 約有 85% 採液冷、15% 採氣冷。

image

Source: Asus, SemiAnalysis

Moreover, there will be a separate version of the cold plate for the Bianca board to support hyperscale custom NICs for backend networking as mentioned earlier. This is because custom NICs replaces the Connect-X NIC and move them to the front of the tray away from the Bianca board.

此外,Bianca board 還會有另一個 cold plate 版本,用來支援前文提到、供 backend networking 使用的 hyperscaler 客製 NIC。原因是客製 NIC 會取代 ConnectX NIC,並從 Bianca board 移到 tray 前方。

There has been a rumor floating around that there is a major heating issue on Bianca. This is mostly overblown. The issue is much smaller than described, and the solution has already been found.

市場上曾流傳 Bianca 有嚴重過熱問題,但這個說法大致被誇大了。實際問題比描述中小得多,而且解決方案已經找到。

Liquid Cooling Form Factors: L2A vs L2L

There are 3 main liquid cooling form factors:

液冷主要有 3 種 form factor:

DLC liquid to air (L2A)

DLC liquid-to-air(L2A)

DLC liquid to liquid (L2L)

DLC liquid-to-liquid(L2L)

Immersion Cooling

The two DLC form factors will be ubiquitous for GB200 deployment. While immersion cooling technology exists, it is not mature enough for mass deployment, and lacks serviceability. Nvidia only recognizes air cooling and DLC as the approved cooling technologies, meaning customers don’t get warranty from Nvidia with immersion cooling. As for now, we have only heard about a few non-GB200 immersion cooling projects in progress in Taiwan, Singapore, and the Middle East (Omniva). These immersion cooling projects must use lower performance / TCO versions of Blackwell.

GB200 部署將普遍採用上述兩種 DLC form factor。雖然 immersion cooling 技術已經存在,但目前成熟度仍不足以大規模部署,而且可維修性較差。Nvidia 只認可氣冷與 DLC 為核准的散熱技術,因此若使用 immersion cooling,客戶無法取得 Nvidia 保固。目前我們只聽說台灣、新加坡與中東(Omniva)有少數非 GB200 的浸沒式散熱專案正在進行,而這些專案必須使用效能/TCO 較低的 Blackwell 版本。

The architecture of the rack between L2A and L2L form factors are mostly similar. As explained before, each IT rack for both L2A and L2L includes cold plates, CDMs, and QDs. The cooling rack/ in-rack CDU is where L2A differs from L2L. In other words, L2A utilizes air as the medium to reject heat from the technology cooling system (TCS), while L2L utilizes facility water as the medium to reject heat from the TCS. TCS represents the cooling system between the IT equipment and the CDU.

L2A 與 L2L 的 IT rack 架構大致相似。如前所述,兩種方案的 IT rack 都包含 cold plate、CDM 與 QD;真正不同的是 cooling rack/in-rack CDU。換句話說,L2A 使用空氣作為介質,把 Technology Cooling System(TCS)的熱排出去;L2L 則使用 facility water 作為排熱介質。TCS 指的是 IT equipment 與 CDU 之間的散熱系統。

L2A has two form factors. The first L2A form factor is the “Rear Door Heat Exchanger” (RDHx), which is an in-rack solution. The second L2A form factor involves a cooling rack, also known as the sidecar.

L2A 有兩種 form factor。第一種是 Rear Door Heat Exchanger(RDHx),屬於 in-rack solution;第二種則使用獨立 cooling rack,也就是 sidecar。

image

Source: SemiAnalysis

In both L2A systems, hot coolant passes through the radiator (heat exchanger), the heat dissipates into the ambient air and gets blown away by the fans, cooling down the coolant. The cooled coolant enters the reservoir and pump units (RPU) and goes back to the cold plate.

在兩種 L2A 系統中,高溫冷卻液都會流經 radiator(heat exchanger),把熱散到周圍空氣,再由風扇把熱空氣吹走,使冷卻液降溫。降溫後的冷卻液進入 reservoir and pump unit(RPU),再送回 cold plate。

RDHx solution has the fans and the radiators attached to the back and the RPU placed at the bottom of the IT rack, while the sidecar solution has these components in a separate cooling rack. Essentially, the side car allows for more radiator space compared to the back of a rack. This reflects the difference between each cooling capacity. RDHx’s cooling capacity is around 30kW-40kw, while Sidecar CDU’s cooling capacity ranges from 70kW to 140kW. We don’t see many uses cases for RDHx as its cooling capacity is way too low to even handle the TDP of one NVL36 rack (66kw). On the other hand, sidecars are designed with capacity at 70kW and 140kW to solve for one NVL36 rack (66kW) and one NVL72 rack (120kW) respectively.

RDHx 方案把風扇與 radiator 安裝在 IT rack 後方,RPU 則放在機櫃底部;sidecar 方案則把這些零組件放在獨立 cooling rack 中。本質上,sidecar 比機櫃後方能提供更大的 radiator 空間,因此兩者散熱能力也不同。RDHx 約可處理 30–40kW,而 sidecar CDU 的散熱能力約為 70–140kW。我們認為 RDHx 的使用情境不多,因為其散熱能力甚至不足以處理單一 NVL36 機櫃 66kW 的 TDP;相較之下,sidecar 分別以 70kW 與 140kW 容量設計,正好對應單一 NVL36(66kW)與單一 NVL72(120kW)。

image

Source: GRCooling

Speaking of rear door heat exchanger (RDHx) liquid cooling solution, some may be confused with another form of air cooling oriented RDHx. From our check, half of the H100 100K cluster shipped to X.ai from Dell adopt this air-cooling enabled RDHx technology, which Elon claimed to be liquid cooling. In fact, Dell shipped what is known as the air to liquid (A2L) RDHx solution. Within the computer tray, it works the same as normal air cooling with 3DVC and fans.

談到 Rear Door Heat Exchanger(RDHx)液冷方案,有些人可能會把它與另一種偏氣冷的 RDHx 混淆。根據我們查核,Dell 出貨給 xAI 的 10 萬顆 H100 cluster 中,約有一半採用這種可搭配氣冷的 RDHx 技術,而 Elon 曾稱它為液冷。實際上 Dell 出貨的是 air-to-liquid(A2L)RDHx;在 compute tray 內部,仍與一般氣冷相同,使用 3DVC 與風扇。

Then, the heat is pulled through the chassis arriving at the heat exchanger (radiator coils) attached to the rear door. Chilled coolant from the CDU gets pumped through the heat exchanger and exchange heat with the hot air. Finally, the warm coolant carries part of the heat toward the CDU to reject heat from the TCS. Usually, the A2L RDHx alone does not have enough cooling capacity to handle all the heat. Hence, the rest of the heat will enter the ambience to be processed by datahall’s air conditioning (CRAC).

接著熱空氣會被抽過機箱,流到安裝在後門上的 heat exchanger(radiator coil)。CDU 送出的低溫冷卻液會被泵送通過 heat exchanger,與熱空氣進行熱交換;升溫後的冷卻液再把部分熱帶回 CDU,將熱從 TCS 排出。通常 A2L RDHx 本身的散熱能力不足以處理全部熱量,因此剩餘熱量仍會排入資料中心環境空氣,由 data hall 的空調系統(CRAC)處理。

image

Source: Motivair

For L2L, there are two form factors, which are with in-rack CDU and in-row CDU. Unlike L2A, L2L coolant does not exchange heat through a radiator; instead, coolant enters the brazed plate heat exchanger (BPHE) in the CDU to exchange heat with facility water. After coolant returns to the RPU from the BPHE.

L2L 有兩種 form factor:in-rack CDU 與 in-row CDU。與 L2A 不同,L2L 的冷卻液不透過 radiator 與空氣交換熱量,而是進入 CDU 內的 brazed plate heat exchanger(BPHE),與 facility water 進行熱交換;之後冷卻液再從 BPHE 回到 RPU。

image

Source: SemiAnalysis

The difference between in-rack and in-row CDU is that in-rack CDU is placed at the bottom of each rack usually taking up ~4RU of rack space, while in-row CDU situates at the end of a rack row. The in-row CDU is connected to all the racks within the row through buried pipelines and has the cooling capacity to reject heat for all the racks. In-rack CDU typically has cooling capacity around 80kW, while in-row CDU has cooling capacity that ranges from 800kW to 2000kW.

in-rack CDU 與 in-row CDU 的差異在於位置與容量。in-rack CDU 通常放在每個 rack 底部,大約占用 4RU 空間;in-row CDU 則設在一整排機櫃的末端,透過埋設管線連接整排所有 rack,並具備為整排機櫃排熱的能力。in-rack CDU 的典型散熱能力約 80kW,而 in-row CDU 約可達 800–2000kW。

Redesigning Data Center Infrastructure for DLC

L2A solution does not require redesigning of data center infrastructure, as heat is dumped into the data center air like traditional air-cooling. The traditional data hall air conditioner/handler (CRAC/CRAH) will remove the heat out of the data hall.

L2A 不需要重新設計資料中心基礎設施,因為它仍像傳統氣冷一樣,把熱排進資料中心空氣,再由既有 data hall air conditioner/handler(CRAC/CRAH)把熱排出 data hall。

image

Source: Schneider

L2L solution, on the contrary, requires more site installation of piping to connect the server racks to the CDU and the CDU to the facility water system. Keep in mind that CRAC/CRAH are still required for L2L as only 85% of heat is removed by liquid, meaning that 15% of heat will enter the data center air. Total data center power consumption can decrease by more than 10.2% when using liquid cooling compared to 100% air-cooling.

相較之下,L2L 需要更多現場管線施工,把 server rack 連到 CDU,再把 CDU 接到 facility water system。需要注意的是,L2L 仍然需要 CRAC/CRAH,因為液體只能帶走約 85% 的熱,剩餘 15% 仍會排進資料中心空氣。與 100% 氣冷相比,採用液冷後,整體資料中心耗電可降低超過 10.2%。

image

Source: Schneider

Moreover, total usage effectiveness (TUE), a more insightful energy efficiency comparative metric between liquid and air cooling, decreases by more than 15%. The TUE for air cooling should be around 1.4 for hyperscalers (~1.55 for neoclouds), while the TUE drops to 1.15 for DLC L2L. With less fans required compared to air cooling and uninterrupted airflow into the data center air, the TUE for DLC L2A should still less than 1.4 of air cooling, which is much higher than 1.15 of DLC L2L as 100% of the heat must be removed by CRAC/CRAH.

此外,total usage effectiveness(TUE)是比較液冷與氣冷能源效率時更有意義的指標,使用液冷後可降低超過 15%。hyperscaler 的氣冷 TUE 約為 1.4,neocloud 約為 1.55;DLC L2L 則可降至 1.15。DLC L2A 因為所需風扇較少、資料中心內氣流阻力也較低,TUE 應仍低於氣冷的 1.4;但由於最終仍需由 CRAC/CRAH 排除 100% 的熱,因此會明顯高於 DLC L2L 的 1.15。

It is obvious that L2L will be the long-term mainstream DLC solution given its energy efficiency and price per W advantage over L2A. However, L2L deployment faces 2 significant delaying factors and bottlenecks now. Firstly, CSPs are prioritizing speed of deployment over TUE gain. Secondly, permitting, which could take time to secure, is required to source water for the facility water system even though the site installation of piping to support L2L is already complete . As a result, the hyperscalers are adopting L2A as the short-term contingency solution to ensure the quick deployment of the GB200 systems. We believe the majority of the GB200 volume will be in L2A form factor before 3Q25.

考量能源效率與每瓦成本優勢,L2L 顯然會成為長期主流 DLC 方案。不過目前 L2L 部署仍面臨兩項主要延遲因素與瓶頸。第一,CSP 現階段更重視部署速度,而不是 TUE 改善;第二,即使支援 L2L 的現場管線已完成,facility water system 的取水仍需取得許可,而審批可能耗時。因此 hyperscaler 短期採用 L2A 作為權宜方案,以確保 GB200 能快速部署。我們認為在 2025 年第三季以前,GB200 大部分出貨仍會採用 L2A form factor。

Liquid Cooling Components Procurement Decision Chain

For liquid cooling components supplier, Nvidia only provides reference design partner for the IT rack listed on a reference vendor list (RVL). They do provide recommended vendors for the cooling rack (CDU), but they are not the same as reference design partners.

在液冷零組件供應商方面,Nvidia 只會針對 IT rack 提供 reference design partner,並列在 Reference Vendor List(RVL)中。對 cooling rack(CDU),Nvidia 也會提供推薦供應商,但這些廠商與 reference design partner 並不是同一概念。

Just like many other components, end customers are not obligated to use Nvidia reference design liquid cooling components. Even with their extremely capable R&D teams, some hyperscalers are relatively unfamiliar with liquid cooling supply chain. Therefore, ODMs or system integrators (SI) have more voice to recommend suppliers for liquid cooling components before the hyperscalers become familiar with the supply chain. There are two working models with unfamiliar liquid cooling components for hyperscalers:

與許多其他零組件一樣,終端客戶並沒有義務採用 Nvidia reference design 的液冷零組件。即使 hyperscaler 擁有非常強的研發團隊,部分業者對液冷供應鏈仍相對陌生,因此在 hyperscaler 尚未熟悉供應鏈之前,ODM 或 system integrator(SI)在推薦液冷零組件供應商時會有更大話語權。對不熟悉液冷零組件的 hyperscaler,主要有兩種合作模式:

ODM suggests suppliers to hyperscalers for qualification.

由 ODM 向 hyperscaler 推薦供應商,再由 hyperscaler 進行 qualification。

Hyperscalers authorize ODM to take responsibility and oversee qualification.

hyperscaler 授權 ODM 負責並管理 qualification 流程。

image

Source: SemiAnalysis

On the other hand, Tier 2 CSP and Neocloud may not have procurement team and R&D capability as adequate as the hyperscalers do. Especially, Neoclouds will rely on OEM like Supermicro, Dell, Lenovo, and HPE that offer no customization. They have two options:

另一方面,Tier 2 CSP 與 neocloud 的採購團隊與研發能力可能不像 hyperscaler 那麼完整。尤其 neocloud 通常會依賴 Supermicro、Dell、Lenovo、HPE 等不提供客製化的 OEM,因此主要有兩種選擇:

Tier 2 CSP can procure from Nvidia’s reference design partners as they have already been qualified by Nvidia.

Tier 2 CSP 可以直接向 Nvidia reference design partner 採購,因為這些供應商已通過 Nvidia qualification。

OEMs offer integrated solutions including DLC components that have been qualified and integrated by the OEMs.

OEM 提供整合式方案,其中包含已由 OEM 完成 qualification 與系統整合的 DLC 零組件。

image

Source: SemiAnalysis

Moreover, the procurement for cooling rack or CDU follows different processes to the IT rack components.

此外,cooling rack 或 CDU 的採購流程,與 IT rack 零組件的採購方式不同。

There are 3 working models for the sidecar (L2A CDU):

sidecar(L2A CDU)主要有 3 種合作模式:

System integrator assembles + system integrator qualified components.

由 system integrator 組裝,並採用 system integrator 自行 qualified 的零組件。

System integrator assembles + end customer qualified components.

由 system integrator 組裝,但採用終端客戶 qualified 的零組件。

Cooling solution suppliers integrated solution + ensuring sidecar integrates well with the IT rack.

由 cooling solution supplier 提供整合式方案,並負責確保 sidecar 能與 IT rack 良好整合。

L2L CDU are delivered fully integrated from supplier:

L2L CDU 則由供應商以完整整合形式交付:

Cooling solution provider integrated solution (Vertiv, Motivair, etc.)

由 cooling solution provider 提供完整整合方案,例如 Vertiv、Motivair 等。

OEM integrated solution (Supermicro, etc)

由 OEM 提供整合式方案,例如 Supermicro 等。

System integrator integrated solution (Ingrasys, etc)

由 system integrator 提供整合式方案,例如 Ingrasys 等。

DLC Components Competitive Landscape Analysis

As the above analysis of the procurement decision indicates, being on the reference vendor list (RVL) doesn’t translate into orders for suppliers. Unless customers are purchasing DGX system, Nvidia doesn’t dictate on components procurement. Ultimately, the decision on suppliers is made by end customers or OEMs based on their procurement strategies. For example, Tier-1 CSPs aim to procure from 1 or 2 suppliers for each liquid cooling component.

如上述採購決策分析所示,列入 Reference Vendor List(RVL)並不等於供應商一定能拿到訂單。除非客戶購買的是 DGX 系統,否則 Nvidia 不會決定零組件採購。最終供應商仍由終端客戶或 OEM 按照各自的採購策略決定。例如 Tier-1 CSP 通常希望每一類液冷零組件只向 1–2 家供應商採購。

At COMPUTEX 2024, over 80 liquid cooling suppliers showcased their liquid cooling solutions as well as production capacity. 5 of us from SemiAnalysis were there and had conversations with every firm.

在 COMPUTEX 2024,超過 80 家液冷供應商展示了各自的液冷方案與生產能力。SemiAnalysis 有 5 位成員到現場,並與每一家廠商都進行了交流。

With some simple math on capacity number, this raised an oversupply concerns before the party even got going. From our supply chain checks, many suppliers claim they have capacity, but very few have been listed on the reference vendor list let alone winning any significant orders. On top of this, quality and track record of the supplier is considered the most important determinant in the procurement decision chain. Hence, each component has varying competitive landscape and qualification entry barrier depending on different level of reliability requirements and customers procurement strategies.

只要簡單把各家宣稱的產能加總,在市場真正起飛前就已經讓人擔心供給過剩。根據我們的供應鏈查核,很多供應商都宣稱自己有產能,但真正列入 RVL 的很少,更不用說拿到具規模的訂單。此外,供應商品質與過往實績被視為採購決策鏈中最重要的因素。因此,依可靠度要求與客戶採購策略不同,每種零組件的競爭格局與 qualification 進入門檻都不相同。

Among the liquid cooling components, cold plate and QDs are where most of the leakage happens, so the hyperscalers are more likely to adopt solution from suppliers on the RVL. As end customers value quality and wish to avoid system failure over prices for components which are an insignificant percentage of GB200 BOM. We believe there will be less competition and pricing pressure on these components. In other words, there are very little incentives for end customers to replace incumbent suppliers at the risk of leakage. The supplier landscape of cold plate will be similar to that of 3DVC, but with some expansion: AVC, Cooler Masters, Delta, and Auras.

在各種液冷零組件中,cold plate 與 QD 是最容易發生漏液的位置,因此 hyperscaler 更可能採用 RVL 上供應商的方案。這些零組件占 GB200 BOM 比例很低,終端客戶更重視品質、避免系統故障,而不是追求最低價格。因此我們認為這些產品的競爭與價格壓力會較小;換句話說,終端客戶幾乎沒有誘因冒著漏液風險去更換既有供應商。cold plate 的供應格局會與 3DVC 類似,但供應商範圍略有擴大,包括 AVC、Cooler Master、Delta 與 Auras。

Suppliers of QD are mostly US/Europe based and the referenced vendors are currently CPC, Parker Hannifin, Danfoss, and Staubli. CPC had purposed built a factory with a clean room for the liquid cooling QDs. Besides the clean room requirement, the QDs have several mechanical IP, including latches and valves to ensure easy access and drip free servicing of the server. At the moment, there is supply tightness of QDs which could become a bottleneck of GB200 shipment.

QD 供應商多數來自美國與歐洲,目前 reference vendor 包括 CPC、Parker Hannifin、Danfoss 與 Staubli。CPC 為液冷 QD 專門興建了一座含 clean room 的工廠。除了 clean room 要求之外,QD 還涉及多項機構 IP,包括 latch 與 valve,以確保伺服器可以方便維修且拆裝時不滴液。目前 QD 供給偏緊,未來可能成為 GB200 出貨的瓶頸。

CDM and CDU are the components that we believe will be more competitive than the cold plate and the quick disconnects. The most important part of the manufacturing process of the CDM is to solder the QDs onto the manifolds properly to prevent leakage. Soldering the QDs is not a difficult process hence the barrier to enter is low. As for the CDU, the components within a L2L CDU, BPHE, and RPU etc, are not difficult for any given supplier to make. However, we believe more established suppliers who provide complete integration of operation with telemetry/monitoring of the system and competent servicing/maintenance capacity will constitute a significant share of the L2L and L2A CDU market.

我們認為 CDM 與 CDU 的競爭會比 cold plate 與 quick disconnect 更激烈。CDM 製造中最重要的環節,是把 QD 正確焊接到 manifold 上以避免漏液;但 QD 焊接本身並不困難,因此進入門檻較低。至於 CDU,L2L CDU 內的 BPHE、RPU 等零組件對一般供應商來說也不難製造。不過我們認為,能提供完整系統整合、telemetry/monitoring,以及具備服務與維護能力的成熟供應商,仍會占據 L2L 與 L2A CDU 市場的重要份額。

Power Delivery Network

As TDP per rack increases from 40kW for H100 4 nodes rack to 120kW GB200 NVL72 rack, power delivery network is centralized on the rack level. Conventionally, high voltage AC is stepped down and converted to 12VDC at node level power supply unit (PSU). For GB200, voltage step down AC to DC conversion happens at the rack level PSUs. The centralized design of GB200 increases power efficiency by 2% compared to conventional design with best-in-class grade PSU.

隨著單櫃 TDP 從 H100、4-node rack 的 40kW,提高到 GB200 NVL72 的 120kW,power delivery network 也改成 rack level 集中式設計。傳統架構是在 node level 的 power supply unit(PSU)把高壓 AC 降壓並轉換成 12V DC;GB200 則在 rack level PSU 完成 AC-to-DC 與降壓。相較採用頂級 PSU 的傳統設計,GB200 的集中式架構可提高約 2% 電力效率。

The gain in efficiency is due to the reduction in oversizing and redundancy factor (excess PSU capacity) on the rack level PSUs compared to node level PSUs. Then by replacing the 12VDC architecture with the 48VDC architecture sending higher voltage into the compute tray, the efficiency is increased by another percent.

效率提升主要來自 rack level PSU 相較 node level PSU,可以降低 oversizing 與 redundancy factor,也就是多餘 PSU 容量。接著再把 12V DC 架構改成 48V DC,以更高電壓把電送進 compute tray,效率還能再提高約 1 個百分點。

Energizing AI: Power Delivery Competition Heats Up Vicor, MPS, Delta, ADI, Renesas, Infineon

Energizing AI: Power Delivery Competition Heats Up Vicor, MPS, Delta, ADI, Renesas, Infineon

Dylan Patel , Myron Xie , and 2 others

Dylan Patel、Myron Xie,以及另外 2 位作者

·

2023年8月1日

Read full story

閱讀完整內容

This is because of the shorter trace length leading to lower resistance loss as discussed in the negative Vicor pieces before. Note after we were negative, the stock fell to more than 50% in just a few months.

原因是 trace length 較短,因此電阻損耗較低,這點我們先前在看空 Vicor 的文章中已經討論過。需要注意的是,在我們表達負面看法之後,該股幾個月內跌幅超過 50%。

image

Source: APC, Schneider

image

Source: Schneider

Power shelves are symmetrically placed at the top and the bottom of the rack for GB200 rack.

GB200 機櫃的 power shelf 會對稱配置在 rack 的頂部與底部。

image

Source: Eaton, SemiAnalysis

Each power shelf consists of 6 PSUs of 5.5kW, which equals to 33kW per power shelf. The power shelf accepts 346-480V AC from the power whip and outputs 48/50V DC, with a maximum current of 600A per power shelf.

每個 power shelf 由 6 顆 5.5kW PSU 組成,因此單個 power shelf 總功率為 33kW。power shelf 從 power whip 接收 346–480V AC,輸出 48/50V DC,單個 power shelf 最大電流為 600A。

image

Source: Eaton

GB200 NVL36 rack will have 2 power shelves per rack supplying 66kW of power, and NVL72 will have 4 power shelves supplying 132kW of power.

GB200 NVL36 每個 rack 配置 2 個 power shelf,總供電能力為 66kW;NVL72 則配置 4 個 power shelf,總供電能力為 132kW。

image

Source: Molex

Each power shelves will send power to the busbar at the rear of the rack running at 1200A. Power will enter the tray from the busbar bar connector at the back of the server tray, then it the cable will bring 48V DC to the power distribution board (PDB). The PDB will step down the DC to 12V and send it too all the board in the compute tray. The Bianca board receives power from the yellow 12V power connector placed at the edges. The fan receives power from the Bianca board through the 8 pin Molex fan connectors.

每個 power shelf 會把電送到機櫃後方、以 1200A 運作的 busbar。電力再從 server tray 後方的 busbar connector 進入 tray,透過線纜把 48V DC 送到 power distribution board(PDB)。PDB 再把 DC 降到 12V,供應 compute tray 內所有板件。Bianca board 從邊緣的黃色 12V power connector 取電,風扇則透過 8-pin Molex fan connector 從 Bianca board 取電。

image

Source: Asus, SemiAnalysis

The supply chain for PDB and VRM on Bianca is quite diverse with even low quality companies such as Alpha Omega getting share on the PDB. The VRM on the Bianca board is much tighter, with the primary share players being Monolithic Power Systems, Renesas, and Infineon. We share more details on price and ASP in the GB200 Component & Supply Chain Model.

Bianca 上 PDB 與 VRM 的供應鏈相當分散,甚至 Alpha Omega 這類品質較低的公司也拿到 PDB 份額。Bianca board 的 VRM 供應則集中許多,主要廠商包括 Monolithic Power Systems、Renesas 與 Infineon。更詳細的價格與 ASP 資訊收錄在 GB200 Component & Supply Chain Model。

BMC

Baseboard management controller (BMC) is a specialized processor with logic control features that is used to remotely monitor and manage host systems. BMC can be accessed remotely via dedicated or shared networks and has multiple connections to the host system, allowing it to monitor hardware via sensors, flash BIOS/UEFI, provide host access via serial or physical/virtual KVM Console. It is able to power cycle and record host and log events. The BMC is used in servers and some datacenter equipment such as NIC, power supplier, DPU and so on.

Baseboard Management Controller(BMC)是一種具邏輯控制功能的專用處理器,用於遠端監控與管理 host system。BMC 可以透過專用或共享網路遠端存取,並與 host system 有多種連線,可透過感測器監控硬體、更新 BIOS/UEFI,或透過 serial、實體/虛擬 KVM console 提供 host access。它也能執行 power cycle,並記錄 host 與系統事件 log。BMC 廣泛使用於伺服器,也存在於 NIC、power supply、DPU 等部分資料中心設備中。

Servers generally have an average of one to two BMCs per general server. For AI servers, the BMC content per server is different based on form factors and SKUs. In this section, we will analyze the BMC content for Nvidia AI servers as well as non-Nvidia AI servers.

一般伺服器平均每台大約配置 1–2 顆 BMC。AI server 則會依 form factor 與 SKU 不同,具有不同的 BMC 含量。本節將分析 Nvidia AI server 與非 Nvidia AI server 的 BMC 含量。

In the GB200 NVL72 reference design with two Bluefield-3, there are 87 BMCs, including:

在配置 2 顆 BlueField-3 的 GB200 NVL72 reference design 中,總共有 87 顆 BMC,包括:

2 to 4 BMCs for compute tray

每個 compute tray 配置 2–4 顆 BMC。

one BMC for HMC (hardware management console),

HMC(Hardware Management Console)配置 1 顆 BMC。

one BMC for DC-SCM (datacenter-ready security control module),

DC-SCM(datacenter-ready security control module)配置 1 顆 BMC。

one BMC for each Bluefield-3 DPU,

每顆 BlueField-3 DPU 配置 1 顆 BMC。

one BMC for each NVSwitch tray,

每個 NVSwitch tray 配置 1 顆 BMC。

one BMC for out of band management switch, and

out-of-band management switch 配置 1 顆 BMC。

one BMC for PDU/power shelves.

PDU/power shelf 配置 1 顆 BMC。

As explained in the previous networking section, very few CSPs and OEMs will do Bluefield-3 for the frontend network. If they adopt Bluefield-3, most would go with a single instead of the dual configuration for the frontend network. For NVL72 without Bluefield-3, there are only 51 BMCs (87 BMCs minus 36 BMCs for Bluefield-3).

如前面 networking 章節所述,真正會在 frontend network 使用 BlueField-3 的 CSP 與 OEM 很少。即使採用,多數也只會配置 1 顆,而不是 reference design 的雙顆配置。若 NVL72 完全不使用 BlueField-3,BMC 數量只剩 51 顆,也就是 87 顆減去 BlueField-3 所對應的 36 顆 BMC。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

Among major buyers, Google, Microsoft, Meta, and AWS will use their custom NICs instead of Bluefield-3 for HGX and NVL72/NVL36. Oracle uses Bluefield-3, but only one Bluefield-3 instead of two for its NVL36 * 2 system. As a result, there are 80 BMCs for Oracle’s NVL36 *2 server, less than 98 BMCs for a reference NVL36*2 form factor.

主要買家中,Google、Microsoft、Meta 與 AWS 在 HGX 及 NVL72/NVL36 上都會使用自家客製 NIC,而不是 BlueField-3。Oracle 會使用 BlueField-3,但在 NVL36 × 2 系統中只配置 1 顆,而不是 2 顆。因此 Oracle 的 NVL36 × 2 server 總共有 80 顆 BMC,低於 reference NVL36×2 form factor 的 98 顆。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

We can use BMC per GPU metric to compare the BMC content of different GB200 SKUs to that of HGX. Even the NVL72 system without Bluefield, which has the least BMC content among GB200 SKUs, has double the BMC to GPU ratio over HGX.

我們可以用每顆 GPU 對應多少 BMC 的指標,比較不同 GB200 SKU 與 HGX 的 BMC 含量。即使是不使用 BlueField、在 GB200 SKU 中 BMC 含量最低的 NVL72,其 BMC/GPU 比率仍是 HGX 的兩倍。

Although the BMC per GPU metric is sufficient to estimate the incremental BMC TAM of the GB200 system, we believe the BMC content increase per CPU metric provides another interesting perspective when analyzing BMC content. The GB200 system without Bluefield-3 have BMC content increase per CPU multiple around 1 times. In other words, BMC content does not increase per CPU from HGX H100 to the GB200 system without the significant incremental BMC content from Bluefield-3.

雖然 BMC/GPU 指標已足以估算 GB200 帶來的增量 BMC TAM,但我們認為從 BMC/CPU 的角度觀察,也能提供另一個有意思的視角。不使用 BlueField-3 的 GB200 系統,其每顆 CPU 對應的 BMC 含量增幅約為 1 倍,也就是說,若扣除 BlueField-3 帶來的大量額外 BMC,從 HGX H100 升級到 GB200,BMC/CPU 並沒有增加。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

In conclusion, the main driver of higher BMC content for GB200 over HGX is the shift from the 2:8 CPU to GPU ratio for HGX to the 2:4 CPU to GPU ratio for GB200. This makes even more sense when you compare the BMC content increase per GPU against the BMC content increase per CPU of the Meta Ariel form factor with a 1:1 CPU to GPU ratio. (Typically, in AI accelerator and general servers, you have 2 CPUs per server chassis and the BMC content is directly tied to the server chassis. This is why it is essential to look at both per CPU and per GPU ratio).

總結來說,GB200 相較 HGX 之所以需要更多 BMC,主要原因是 CPU:GPU 比例從 HGX 的 2:8,改成 GB200 的 2:4。若再拿 CPU:GPU 為 1:1 的 Meta Ariel form factor,比較 BMC/GPU 與 BMC/CPU 的增幅,這個關係會更加清楚。一般 AI accelerator server 與通用伺服器通常每個 chassis 配置 2 顆 CPU,而 BMC 含量本質上與 server chassis 數量直接相關,因此同時觀察每 CPU 與每 GPU 的比率非常重要。

We share estimates of the year-over-year change in BMC demands for general servers and AI servers based on the GPU/accelerator shipments in our Accelerator Model and our GB200 Component & Supply Chain Model . This includes the BMC breakdown for each client’s different AI form factors, as discussed above.

我們根據 Accelerator Model 中的 GPU/accelerator 出貨量,以及 GB200 Component & Supply Chain Model,估算一般伺服器與 AI server 的 BMC 需求年增率,其中也包含前述各家客戶不同 AI form factor 的 BMC 拆解。

Key Assumptions for this estimation:

此估算的主要假設如下:

For HGX/NVL36/NVL72 servers for Google, Microsoft, AWS, Meta and Oracle, we calculate the BMC demand based on their system designs.

Google、Microsoft、AWS、Meta 與 Oracle 的 HGX/NVL36/NVL72 server,BMC 需求依各家公司實際 system design 估算。

For HGX/NVL36/NVL72 for other buyers, we estimate usage of Bluefield-3, with our assumptions in the table below.

其他買家的 HGX/NVL36/NVL72,則按照下表假設估算 BlueField-3 的使用量。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

For other AI servers, the majority will have an average of 2.8 BMCs, the same as HGX.

其他 AI server 大多平均配置 2.8 顆 BMC,與 HGX 相同。

For general servers we assume a 10% recovery in 2024 and 5% in 2025.

一般伺服器部分,我們假設 2024 年需求回升 10%,2025 年再成長 5%。

Given the assumption, our model estimates total BMC shipments increase in 2025, mainly driven by the 64% growth of BMC units for Nvidia-based AI servers. Other AI servers’ BMC demand should also grow. In terms of market size, the Nvidia NVL36/72 systems will increase BMC TAM in 2025, but our estimates differ from the street.

根據上述假設,我們的模型估計 2025 年 BMC 總出貨量將成長,主要由 Nvidia-based AI server 的 BMC 數量成長 64% 所推動。其他 AI server 的 BMC 需求也應會增加。從市場規模來看,Nvidia NVL36/72 系統確實會在 2025 年擴大 BMC TAM,但我們的估算與市場共識有所不同。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

Consensus assumption of the capital market is that the majority or even all NVL36/72 servers will follow Nvidia’s reference design adopting Bluefield-3. However, this is incorrect as the major CSPs will have their custom NICs solutions instead of the Nvidia DPU. A sensitivity analysis must be done to see the upsides if other buyers (non-Google/Microsoft/Meta/AWS/Oracle) use more Bluefield-3. With 20% more buyers using Bluefield-3 based on Nvidia reference design, the BMC units would increase by 25k units, implying 0.5% upside to AI server BMC demand, or just 0.1% upside to total BMC market. If other buyers 100% follow Nvidia’s reference design, the upside to would be 11% for AI-related BMC volume, or only 2% for total BMC volume. In other word, even if other (non-Google/Microsoft/Meta/AWS/Oracle) buyer all adopt the Bluefield-3 DPU solution for their GB200 racks, the total BMC shipment would not increase significantly. This is because that BMC for AI servers only accounts for roughly 17% of BMC shipments only.

資本市場的共識假設是,大多數甚至全部 NVL36/72 server 都會照 Nvidia reference design 採用 BlueField-3。但這個假設不正確,因為主要 CSP 會使用自家客製 NIC,而不是 Nvidia DPU。若要評估其他買家(不含 Google/Microsoft/Meta/AWS/Oracle)提高 BlueField-3 採用率所帶來的上行空間,需要做敏感度分析。若採用 Nvidia reference design、使用 BlueField-3 的其他買家增加 20%,BMC 數量只會增加約 2.5 萬顆,相當於 AI server BMC 需求上行 0.5%,或整體 BMC 市場僅上行 0.1%。即使其他買家 100% 採用 Nvidia reference design,AI-related BMC volume 的上行也只有 11%,整體 BMC volume 則約 2%。換句話說,即使所有非 Google/Microsoft/Meta/AWS/Oracle 的買家都在 GB200 rack 採用 BlueField-3 DPU,BMC 總出貨量也不會顯著增加,因為 AI server BMC 原本只占整體 BMC 出貨約 17%。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

In an unrealistic scenario where all NVL36/72 buyers including Google/Microsoft/Meta/AWS/Oracle all follow Nvidia’s reference design in adopting Bluefield-3, they would require an additional 854k units of BMC, representing 18% upside to AI server BMC demand, or 3% upside to total BMC demand. This would drive the total BMC volume to grow 12% in 2025.

在一個不太現實的情境下,若所有 NVL36/72 買家,包括 Google/Microsoft/Meta/AWS/Oracle,都完全依照 Nvidia reference design 採用 BlueField-3,則會額外需要 85.4 萬顆 BMC,相當於 AI server BMC 需求增加 18%,或整體 BMC 需求增加 3%。在這種情況下,2025 年 BMC 總出貨量將成長 12%。

image

Source: SemiAnalysis GB200 Component & Supply Chain Model

Mechanical Components

The two main mechanical components are the chassis and the rail kit. These both benefitted from significant content increases for HGX H100 given the higher 5U-8U chassis and considerable weight that comes with the 3DVC compared to a 1U-2U traditional server. Hence, the chassis and rail kit ASP for HGX both went up ~10 times compared to traditional server.

兩個主要機構件是 chassis 與 rail kit。HGX H100 因為使用 3DVC,機箱高度提高到 5U–8U,整機重量也遠高於傳統 1U–2U server,因此 chassis 與 rail kit 的價值量都顯著增加。HGX 的 chassis 與 rail kit ASP 相較傳統 server 約提高 10 倍。

image

Source: Oracle

With the liquid cooling of GB200 architecture, high 5U-8U chassis and high spec rail kit are not necessary not suitable anymore. Hence, the rail kit content is downgraded from HGX to GB200, with a more similar spec to the traditional server. King Slide has an extremely solid technological and IP leadership over its competitors especially for high 5U-8U rail kit, in which King Slide has high share of HGX rail kit. Its 60% gross margin for lower spec 1U or 2U traditional and over 60% gross margin for 5U+ AI server rail kit reflects its pricing power. Note there is a content increase for 10U B200 liquid cooled servers.

GB200 採用液冷後,5U–8U 的高機箱與高規格 rail kit 已不再需要,也不再適合。因此從 HGX 升級到 GB200,rail kit 的價值量反而下降,規格更接近傳統 server。King Slide 在技術與 IP 上相對競爭對手具有非常穩固的領先優勢,尤其是在 5U–8U 高規格 rail kit,因此在 HGX rail kit 市場占有高份額。公司在較低規格的 1U/2U 傳統產品毛利率約 60%,5U+ AI server rail kit 毛利率更超過 60%,反映其定價能力。需要注意的是,10U B200 液冷 server 的 rail kit 價值量仍會增加。

Although Nan Juen(Repon) is still slightly behind King Slide in terms of IP for the 5U+ rail kit, it will gain share from King Slide at GB200 due to the lower IP barrier to overcome. However, this is unlikely to drive the pricing down as Nan Juen’s pricing is only slightly less than King Slide who determine the pricing for the market.

雖然 Nan Juen(Repon)在 5U+ rail kit 的 IP 能力上仍略落後 King Slide,但 GB200 因規格降低、IP 進入門檻下降,因此 Nan Juen 將從 King Slide 手中取得部分份額。不過這不太可能明顯壓低價格,因為 Nan Juen 的報價只比 King Slide 略低,而市場定價仍主要由 King Slide 主導。

The chassis will have slightly better pricing than the traditional server of the same height due to better material and thicker chassis for GB200 compute tray. The main players of chassis for GB200 will be Chenbro and AVC. Note players like Ingrasys will make their own chassis.

GB200 compute tray 因材料較好、chassis 也更厚,因此同樣高度下的 chassis 價格會略高於傳統 server。GB200 chassis 的主要供應商將是 Chenbro 與 AVC;另外像 Ingrasys 這類業者也會自行製造 chassis。

OEM / ODM Mapping

OEM and ODM details are also very important as there is a big shift generation on generation. There is a fear from some that OEMs get much weaker. This is not the case because complexity of deployments is much higher. Another fear is that Quanta loses tons of share to Ingrasys, but that is only at Microsoft. We have all these details and more in the GB200 Component & Supply Chain Model.

OEM 與 ODM 的細節同樣非常重要,因為這一代的供應格局有很大變化。有人擔心 OEM 的角色會大幅削弱,但我們認為並非如此,因為部署複雜度反而明顯提高。另一個擔憂是 Quanta 會大量流失份額給 Ingrasys,但這種情況主要只發生在 Microsoft。我們在 GB200 Component & Supply Chain Model 中整理了這些細節以及更多供應鏈資訊。

Get 20% off a group subscription

團體訂閱可享 8 折優惠

GB200 Component & Supply Chain Model

Dylan Patel

·

2024年7月16日

The SemiAnalysis GB200 Component & Supply Chain BoM Model details the components within a GB200 NVL72/NVL36 system as well as the different customized SKUs. We provide pricing and quantity of each component, which differs depending on the GB200 SKU. We also map out the supplier landscape for each component. The quantity of components and BoM costs for e…