For the VR NVL72 reference design, the power delivery infrastructure at the rack level includes four 110kW power shelves.
Evidence
Context After
The design with four 110kW power shelves is an N+1 redundancy approach. Each 110kW power shelf is 3U tall and includes six 18.3kW PSU with built in capacitors in the PSU. Each power shelf receives three phase 415VAC-480VAC of power from two 100A whips.