Compute Tray: Power Delivery - Line hint:
338
Context Before
As the Strata board draws around 4800W of power (equivalent to the TDP of half a general server rack) versus Bianca at 3000W, it is necessary to deliver power to the board at a higher voltage.
Evidence
The benefit of moving 50VDC-12VDC conversion closer is to the reduce current and increase transmission efficiency.
Context After
96 Amps at 50V has 17x lower power loss than 400A at 12V due to the quadratic relationship between power loss and current.